3
EN - 24 - For the installer
(Malfunction) information values
Submenu
Description
Minimum
Maximum
Default
P75
General reset.
•
Press
"
" on the CC ease
panel for 5 seconds to carry
out a general reset.
All original factory settings are re-
stored following a general reset.
0
1
0
Note:
After a general reset, the ComfoAir will ask you to reset the “nL / HL” (see
P56) and “Li / Re” (see P57) settings.
Following a general reset, all settings in menus P2 and P3 and the pro-
grammes in P5 and P6 will need to be reset.
If the ComfoAir is
fi
tted with a pre-heater, this must be recon
fi
rmed in menu
P51, as this setting defaults to not
fi
tted after a general reset.
P76
Self-test of the ComfoAir.
0
1
0
Note:
Directly after activation of the self-test, the ComfoAir switches to its highest speed.
Immediately after activating the self-test, the bypass valve opens and closes. If the
self-test is successful, the valve of the pre-heater opens and closes (if fi tted).
P77
Resetting fi lter dirty counter.
0
1
0
Note:
This resets the counter that triggers a dirty fi lter alert on the ComfoAir. This allows the
fi lter to be cleaned or replaced before the dirty fi lter alert appears.
Menu P8
Settings
(Malfunction) information values
Series No.
Description
Minimum
Maximum
Default
810
Analogue input 1
0= not fi tted 1 = fi tted
0 1 0
811
0= control 1 = programme
(analogue input )
0 1 0
812
set point analogue input 1
(programme)
0 100
50
813
min. setting analogue input 1
0
99
0
814
max. setting analogue input 1
0
100
100
815
0=positive analogue input 1
1=negative setting analogue
input 1
0 1 0
816
read-out analogue input 1
0
100
-
820
Analogue input 2
0= not fi tted 1 = fi tted
0 1 0
821
0= control 1 = programme
(analogue input 2)
0 1 0
822
set point analogue input 2
(programme)
0 100
50
823
min. setting analogue input 2
0
99
0
824
max. setting analogue input 2
0
100
100
825
0=positive analogue input 2
1=negative setting analogue
input 2
0 1 0
826
read-out analogue input 2
0
100
-
830
Analogue input 3
0= not fi tted 1 = fi tted
0 1 0
831
0= control 1 = programme
(analogue input 3)
0 1 0
Содержание ComfoAir 550 Luxe