If the machine is a forklift, check the performance with and without load.
9)
RELEASE BRAKING. Operate the machine at full speed. Release the
accelerator pedal. Adjust the level to your requirements. If the machine is a
forklift, check the performance with and without load.
10)
INVERSION BRAKING. Operate the machine at 25% full speed. Whilst
travelling INVERT the Direction Switch. Set a soft Level of Inversion Braking.
When satisfactory, operate the machine at Full Speed and repeat. If the
machine is a Forklift, repeat the tests and make adjustments with and without
load. The unlade full speed condition should be the most representative
condition.
11)
PEDAL BRAKING (If used). Operate the machine at full Speed. Release the
accelerator pedal and press the Pedal Brake. Set braking level to your
requirements.
12)
Set “MAX SPEED FORW”.
13)
Set “MAX SPEED BACK” (Reverse).
14)
Make the choice for the truck behaviour on a slope (see chapter 5.4). If the
"Stop on ramp" option is ON, set the desired value of "auxiliary time"
parameter.
15)
Set “SET TEMPERATURE”, setting the motor thermal sensor type used.
5.9 Sequence for Ac Inverter Pump setting
When the "Key Switch" is closed, if no alarms or errors are present, the Console
Display will be showing the Standard Zapi Opening Display.
If the controller is not configured to your requirements, follow the sequence
detailed here following. Remember to re-cycle the Key Switch if you make any
changes to the controller’s configuration.
1)
Select the Options required. See Chapter 5.4.2.
2)
Select and set the Battery Voltage. See Chapter 5.4.2.
3)
Confirm correct installation of all wires. Use the Console’s TESTER function
to assist.
4)
Perform the lift signal acquisition procedure using the Console “PROGRAM
VACC”. Procedure is detailed on Chapter 6.4.
5)
Set the "MAXIMUM CURRENT” Current, using the table on Chapter 5.6.
6)
Set the Acceleration and Deceleration Delay requirements for the pump.
7)
Set the “MIN SPEED UP” level starting from 0 Hz. The pump should just turn
when the request microswitch is closed. Increase the level accordingly.
8)
Set the Speed Reductions as required. Make adjustments to “CUTBACK
SPEED”. Check the performance with the full request. Check the
performance with and without load.
9)
Set “MAX SPEED UP” (max speed of pump motor).
10)
Set “HYD SPEED FINE” to adjust the hydraulic steering speed (pump motor
speed when HYDRO function is requested).
11)
Set “AUXILIARY TIME” (time delay before pump stops when an hydraulic
steering function request is switched off).
12)
Set “SET TEMPERATURE”, setting the motor thermal sensor type used.
5.10 Tester: description of the function; Traction configuration
The most important input or output signals can be measured in real time using
the TESTER function of the console. The Console acts as a multimeter able to
ADEZP0AE - AC-2 INVERTER - User Manual
Page - 43/64
Содержание AC-2
Страница 21: ...4 8 Mechanical drawing ADEZP0AE AC 2 INVERTER User Manual Page 21 64...
Страница 22: ...4 9 Connection drawing Traction configuration Page 22 64 ADEZP0AE AC 2 INVERTER User Manual...
Страница 23: ...4 10Connection drawing Pump configuration ADEZP0AE AC 2 INVERTER User Manual Page 23 64...
Страница 24: ...4 11Connection drawing Combi configuration Page 24 64 ADEZP0AE AC 2 INVERTER User Manual...
Страница 49: ...12 Press OUT to return to the Opening Zapi Display ADEZP0AE AC 2 INVERTER User Manual Page 49 64...