6.3 Description of “ALARMS” menu
The microprocessor in the controller remembers the last five Alarms that have
occurred. Items remembered relative to each Alarm are: the code of the alarm,
the number of times the particular Alarm occurred, the Hour Meter count, and the
controller temperature.
This function permits a deeper diagnosis of problems as the recent history can
now be accessed.
Flow Chart showing how to use the ALARMS function via the Digital Console.
1) Opening Zapi Display.
AC2 ZAPI V0.0
48V 350A 00000
2) Press ENTER to go into the General menu.
' % '
' ' '
3) The Display will show:
MAIN MENU
PARAMETER CHANGE
4) Press ROLL UP or ROLL DOWN button until
PARAMETER CHANGE appears on the display.
% ' '
% ' '
5) The Display will show:
MAIN MENU
ALARMS
6) Press ENTER to go into the ALARMS function.
' % '
' ' '
7) The Display will show the most recent Alarm.
CODE
00005 #02 20°C
8) Each press of the ROLL UP button brings up
following Alarms. Pressing ROLL DOWN returns to
the most recent.
% ' '
% ' '
9) If an Alarm has not occurred, the Display will
show: ALARM NULL.
CODE
00007 #03 18°C
10) When you have finished looking at the Alarms,
press OUT to exit the ALARMS menu.
' ' '
' % '
11) The Display will ask “CLEAR LOGBOOK?”.
CLEAR LOGBOOK?
YES=ENTER NO=OUT
12) Press ENTER for yes, or OUT for NO.
' % '
' ' '
' ' '
' % '
13) Press OUT to return to the Opening Zapi
Display.
' ' '
' % '
Page - 52/64
ADEZP0AE - AC-2 INVERTER - User Manual
Содержание AC-2
Страница 21: ...4 8 Mechanical drawing ADEZP0AE AC 2 INVERTER User Manual Page 21 64...
Страница 22: ...4 9 Connection drawing Traction configuration Page 22 64 ADEZP0AE AC 2 INVERTER User Manual...
Страница 23: ...4 10Connection drawing Pump configuration ADEZP0AE AC 2 INVERTER User Manual Page 23 64...
Страница 24: ...4 11Connection drawing Combi configuration Page 24 64 ADEZP0AE AC 2 INVERTER User Manual...
Страница 49: ...12 Press OUT to return to the Opening Zapi Display ADEZP0AE AC 2 INVERTER User Manual Page 49 64...