Table 50: Display only
Field/LED name
Description
ACC Surge Detected (LED)
Only displayed if equipped with a VSD or MVVSD. Illuminates
momentarily when a surge is detected by the ACC function in
the Microboard, while the drive is running at less than maximum
frequency.
VGD Count
Displays the number of times the Stall Detector Board output
voltage goes above the High Limit Setpoint. The count can be
cleared with an ADMIN access level using the VGD CYCLE COUNT
key on the VGD SETPOINTS Screen.
VGD Time ( __Days __Hrs
__Min __Sec)
Displays the accumulated time the Stall Detector Board output
voltage is greater than the High Limit Setpoint while the chiller is
running.
Control Status
Displays the current state of the VGD control. The states are: Stall
Waiting, Stall Reacting, Probing, Surge Reacting, Surge Waiting, Hot
Gas Override.
Time Remaining
While the VGD is in the Stall Waiting State, displays the time
remaining in the Probe Wait Time interval (value programmed as
the Probe Wait Time setpoint).
Diffuser Gap Control Mode Indicates whether the VGD is under manual or automatic control.
Table 51: Programmable
Button
Access level Description
[VGD] Open
(Manual)
Service
This key puts the VGD in manual mode and sends an OPEN
command to the VGD
[VGD] Close
(Manual)
Service
This key puts the VGD in manual mode and sends a CLOSE
command to the VGD.
[VGD] Hold
(Manual)
Service
This key puts the VGD in manual mode and sends a HOLD command
to the VGD.
Table 52: Navigation
Button
Access Level Description
Home
View
Returns user to HOME Screen.
Compressor View
Returns user to COMPRESSOR Screen.
VGD
Setpoints
Service
Move to the subscreen that allows programming of the Variable
Geometry Diffuser setpoints
65
YK-EP Style B Centrifugal Chiller
Содержание YK-EP
Страница 2: ...2 YK EP Style B Centrifugal Chiller...
Страница 6: ...6 YK EP Style B Centrifugal Chiller...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260...