
Table 141: Programmable
Button
Access level Description
Motor
Comm.
Protocol
Service
VSD and MVVSD applications – Should be set to Modbus.
Style B Liquid Cooled Solid State Starter and MVSSS applications –
Should be set to Modbus.
Only displayed when Motor Drive Type Setpoint above is selected
as “VSD-60 Hz”, “VSD-50 Hz”, “MVVSD”, “SSS-Mod B”or “MV SSS”.
Allows the Service Technician to enable the appropriate serial
communications port for communications with the Solid State
Starter (SSS) or Variable Speed Drive (VSD). The chiller must be
stopped with the Start-Run-Stop/Reset switch in the Stop/Reset
position to change this setpoint.
Coastdown
Time
Service
Only displayed when Standard is selected as the Coastdown
Setpoint. Allows Service Technician to select appropriate coastdown
time for compressor motor applied. Larger motors require a
longer coastdown time to assure the motor rotation has stopped
before the oil pump is turned off at completion of post-lube.
Programmable range is determined by the Chiller Style/Compressor
Setpoint (Style F/J7 and G/K6-K7, the range is 240 (default) to 900
seconds. All others, the range is 150 (default) to 900 seconds).
Condenser
Temperature
Range
Service
Special order R134a chillers are allowed to operate at higher than
standard condenser temperatures. The resulting higher operating
pressures require higher condenser warning and safety shutdown
thresholds than standard applications. These chillers are equipped
with a special High Pressure Cutout Switch (HPCO) that can be set to
trip at a higher pressure.
This setpoint allows for either standard or higher temperature
condenser temperature operation. It is set to Extended for those
chillers equipped for high condenser temperature operation.
Otherwise, it is set to Standard. For R134a chillers, refer to Table 142.
Motor Auto
Lube Type
Service
Set to None, QLS401, P203 or Sleeve as applicable:
•
None - User must manually lubricate the motor bearings.
•
QLS401 - Injects grease at the interval factory set in the
QLS401 system.
•
P203 - The OptiView panel controls the lubrication time
interval and also monitors the grease level.
•
Sleeve - Motors with sleeve bearings use a lubricating oil
which extends the time interval for bearing lubrication.
Table 142: Condenser temperature range
Setpoint
Standard
Extended
Warning – High Pressure Limit – Maximum allowable value (PSIG) 162.5
193
Condenser – High Pressure – Trip/reset threshold (PSIG)
180/120
200/140
Condenser – High Pressure Stopped – Trip/reset threshold (PSIG) 160/160
170/170
147
YK-EP Style B Centrifugal Chiller
Содержание YK-EP
Страница 2: ...2 YK EP Style B Centrifugal Chiller...
Страница 6: ...6 YK EP Style B Centrifugal Chiller...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260...