Table 68: Display only
Field/LED
name
Access level Description
Sump Oil
Pressure
(LOP)
–
Displays the low side oil pressure measured at the sump.
Oil Pump
Run Output
(LED)
–
Indicates whether the oil pump is being commanded to operate.
Oil Return
Solenoid
(LED)
–
Indicates whether the solenoid is energized.
Oil Heater
(LED)
–
(Variable Speed Oil Pump Only) Indicates whether the oil heater
output is energized.
Oil Seal
Lubrication
Time
Remaining
Service
If a Seal Lubrication is in progress, this will display the amount of
time remaining in the lubrication process.
Next Oil Seal
Lubrication
Service
This display will show the time remaining until the next Seal
Lubrication is necessary, when this function is enabled.
Setpoint Oil
Pressure
–
(Variable Speed Oil Pump Only) The Variable Speed Oil Pump
(VSOP), if installed, operates to control to a defined Oil Pressure
value. During prelube, and for the first 15 seconds after prelube, this
setpoint value is 45.0 PSID. During this time, this field will display
the target value. After 15 seconds, this value will display the user-
programmed setpoint Oil Pressure.
Variable
Speed
Oil Pump
Control
Mode
–
(Variable Speed Oil Pump Only) Indicates whether the Variable
Speed Oil Pump speed is under manual or automatic control.
Oil Pump
Drive
Command
Frequency
–
(Variable Speed Oil Pump Only) Displays the actual speed command
being sent to the VSOP. This value could be the result of automatic
control based on the Oil Pressure Setpoint, or the result of a manual
speed command.
Manual
Oil Pump
Operation
Time Left
–
Displays the time remaining in the 10-minute Manual Oil Pump
operation described below.
YK-EP Style B Centrifugal Chiller
80
Содержание YK-EP
Страница 2: ...2 YK EP Style B Centrifugal Chiller...
Страница 6: ...6 YK EP Style B Centrifugal Chiller...
Страница 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Страница 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Страница 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Страница 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Страница 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Страница 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Страница 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Страница 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Страница 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Страница 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...
Страница 260: ...Figure 87 Microboard 031 03630 007 Figure 88 Program card 031 03601 002 YK EP Style B Centrifugal Chiller 260...