74
YORK INTERNATIONAL
GENERAL
The PRINT keys allow the operator to obtain a remote
print-out of real-time system operating data and a print-
out of system data at the instant of the fault on the last
three faults which occurred on the chiller.
If a remote printer is not being used, or the desire is to
obtain data locally at the panel, the same keys allow
access to identical fault data. Identical and additional
real-time information is available by using a combination
of the PRINT keys and the other keys on the keypad.
An explanation of the use of the keys for remote printer
or local data retrieval will follow. An optional printer (Page
95) will be required for remote printout.
NOTE: Some of the information that may be recovered
(i.e. fan operation, discharge pressures, stages
of loading etc.) may not apply to the chiller. The
micro is capable of operating these items and
displaying information relating to them regard-
less of whether they are present on the chiller.
REMOTE PRINTOUT
Oper Data
The OPER DATA key allows the operator to remotely
obtain a printout of current system operating parame-
ters. When the key is pressed, a snapshot will be taken
of system operating conditions and panel programming
selections. This data will be temporarily stored in mem-
ory and transmission of this data will begin to the re-
mote printer. As the data is transmitted, it will be erased
from memory.
A sample printout is shown in Fig. 23.
PRINT KEYS
FIG. 23
OPERATING DATA PRINTOUT
26572A(D)
PRINT
KEYS
OPER
DATA
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 4/17/98
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP
65.0 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
50 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
143 PSIG
OIL PRESSURE
75 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
0 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
80 PSIG
OIL PRESSURE
1 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
✱
=HOLIDAY
SUN START=06:00AM
STOP=11:00PM
MON START=06:00AM
STOP=11:00PM
TUE
START=06:00AM
STOP=11:00PM
WED START=06:00AM
STOP=11:00PM
THU START=06:00AM
STOP=11:00PM
FRI
START=06:00AM
STOP=11:00PM
SAT
START=06:00AM
STOP=11:00PM
HOL START=00:00AM
STOP=00:00AM
Содержание YCRJ45E00
Страница 29: ...FORM 150 24 NM27 YORK INTERNATIONAL 29 CONTROL CIRCUIT With I O Expansion Board LD02106 ...
Страница 30: ...30 YORK INTERNATIONAL FIG 9 SYSTEM WIRING ...
Страница 31: ...FORM 150 24 NM27 YORK INTERNATIONAL 31 LD02678 ...
Страница 33: ...FORM 150 24 NM27 YORK INTERNATIONAL 33 LD02357 MOTOR TERMINAL BOX WIRING WITH MODEL 31AA MOTOR PROTECTOR ...
Страница 34: ...34 YORK INTERNATIONAL FIG 10 CONNECTION DIAGRAM LD02358 MICROPANEL CONNECTION DIAGRAM WITHOUT EXPANSION BOARD ...
Страница 35: ...FORM 150 24 NM27 YORK INTERNATIONAL 35 LD02679 ...
Страница 36: ...36 YORK INTERNATIONAL MICROPANEL CONNECTION DIAGRAM With I O Expansion Board LD02107 ...
Страница 37: ...FORM 150 24 NM27 YORK INTERNATIONAL 37 LD02108 ...