![York YCRJ45E00 Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/york/ycrj45e00/ycrj45e00_installation-operation-and-maintenance_912707091.webp)
FORM 150.24-NM27
YORK INTERNATIONAL
91
to see if any system safeties have been exceeded.
If all conditions allow for start, the lead compressor
will start unloaded coincident with the start, the pro-
grammable anti-recycle timer will be set and begin
counting downward to 0. The liquid line solenoid of
the lead compressor will be open.
5.
After 4 seconds of run time,
the motor current of
the lead compressor must be >14% FLA and <115%
FLA. Oil pressure must be >5 PSID. If these condi-
tions are not met, the lead compressor will shut
down.
6.
After 30 seconds of run time,
the oil pressure of
the lead compressor must be >20 PSID and the
suction pressure must be >50% of cut-out. If these
conditions are not met, the lead compressor will
shut down.
7.
After 2 minutes and 30 seconds of run time,
the
lead compressor will load the 1st step, if cooling
demand (temperature and rate control) requires.
8.
After 4 minutes of operation,
the oil pressure of
the lead compressor must be >25 PSID and the
suction pressure must be > cut-out. If these condi-
tions are not met, the lead compressor will shut
down.
9.
After 5 minutes of run time,
the lead compressor
will load the second step, if cooling demand (tem-
perature and rate control) requires.
10.
After 7 minutes and 30 seconds of run time,
the
lead compressor will load its 3rd step if tempera-
ture demand (temperature and rate control) requires.
11.
After 10 minutes of run time,
if cooling demand
requires (temperature and rate control), the lag com-
pressor will start unloaded and its anti-recycle
counter will begin counting back to 0. The liquid
line solenoid will open. The lead compressor will
unload two steps to its 1st step of 3 loading steps.
12.
After 10 minutes and 4 seconds of run time,
the
motor current of the lag compressor must be >14%
FLA and <115% FLA. Oil pressure must be >5 PSID.
If these conditions are not met, the lag compressor
will shut down.
13.
After 10 minutes and 30 seconds of run time,
the oil pressure of the lag compressor must be >20
PSID and the suction pressure must be >50% cut-
out. If these conditions are not met, the lag com-
pressor will shut down.
14.
After 12 minutes and 30 seconds of run time,
the lag compressor will load to the 1st step of load-
ing, if cooling demand requires (temperature and
rate control). The lead compressor remains un-
changed at the 1st step of loading.
15.
After 14 minutes of operation,
the oil pressure of
the lag compressor must be >25 PSID and the suc-
tion pressure must be > cut-out. If these conditions
are not met, the lag compressor will shut down.
16.
After 15 minutes of run time,
the lead compres-
sor will load to its 2nd step of loading, if cooling
demand requires (temperature and rate control). The
lag compressor remains unchanged at the 1st step
of loading.
17.
After 17 minutes and 30 seconds of run time,
the lag compressor will load to its 2nd step of load-
ing, if cooling demand requires (temperature and
rate control). The lead compressor remains un-
changed at the 2nd step of loading.
18.
After 20 minutes of run time,
the lead compres-
sor will load to its 3rd and final step of loading, if
cooling demand requires (temperature and rate con-
trol). The lag compressor remains unchanged at the
2nd step of loading.
19.
After 22 minutes and 30 seconds of run time,
the lag compressor will load to its 3rd and final step,
if cooling demand requires (temperature and rate
control). The lead compressor remains unchanged
at the 3rd step of loading.
Содержание YCRJ45E00
Страница 29: ...FORM 150 24 NM27 YORK INTERNATIONAL 29 CONTROL CIRCUIT With I O Expansion Board LD02106 ...
Страница 30: ...30 YORK INTERNATIONAL FIG 9 SYSTEM WIRING ...
Страница 31: ...FORM 150 24 NM27 YORK INTERNATIONAL 31 LD02678 ...
Страница 33: ...FORM 150 24 NM27 YORK INTERNATIONAL 33 LD02357 MOTOR TERMINAL BOX WIRING WITH MODEL 31AA MOTOR PROTECTOR ...
Страница 34: ...34 YORK INTERNATIONAL FIG 10 CONNECTION DIAGRAM LD02358 MICROPANEL CONNECTION DIAGRAM WITHOUT EXPANSION BOARD ...
Страница 35: ...FORM 150 24 NM27 YORK INTERNATIONAL 35 LD02679 ...
Страница 36: ...36 YORK INTERNATIONAL MICROPANEL CONNECTION DIAGRAM With I O Expansion Board LD02107 ...
Страница 37: ...FORM 150 24 NM27 YORK INTERNATIONAL 37 LD02108 ...