JOHNSON CONTROLS
58
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
PHYSICAL DATA (ENGLISH - STANDARD EFFICIENCY)
REFRIGERANT R-134a
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P/H)
GENERAL UNIT DATA
60 HZ
0157
0177
0187
0207
0227
0247
0267
Number of Independent Refrigerant Circuits
2
2
2
2
2
2
2
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, lb
162/162 170/170 185/170 192/175 192/192 230/195 230/230
Oil Charge, Ckt.-1/Ckt.-2, gal
5/5
5/5
5/5
5/5
5/5
5/5
5/5
Compressors, Semi-hermetic Screw Qty per
Chiller
2
2
2
2
2
2
2
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, ft
2
235
235
264
264
293
323
352
Number of Rows
3
3
3
3
3
3
3
Fins per Inch
17
17
17
17
17
17
17
Condenser Fans
Number, Ckt.-1/Ckt.-2
4/4
4/4
5/4
5/4
5/5
6/5
6/6
Low Noise Fans
Fan Motor, hp
2
2
2
2
2
2
2
Total Chiller Airflow, cfm
104000
104000
117000
117000
130000
143000
156000
ULTRA QUIET FANS
Fan Motor, HP
2
2
2
2
2
2
2
Total Chiller Airflow, cfm
104000
104000
117000
117000
130000
143000
156000
Dual Speed Fans - Normal Speed
Fan Motor, hp
2
2
2
2
2
2
2
Total Chiller, CFM
88000
88000
99000
99000
110000
121000
132000
Dual Speed Fans - Lower Speed
Fan Motor, hp
2
2
2
2
2
2
2
Total Chiller, CFM
67200
67200
75600
75600
84000
92400
100800
High Static Fans
Fan Motor, hp
5
5
5
5
5
5
5
Total Chiller, CFM
104000
104000
117000
117000
130000
143000
156000
Evaporator, Direct Expansion
Water Volume, gal
67.0
95.0
95.0
140.0
140.0
140.0
140.0
Maximum Water Side Pressure, psig
150
150
150
150
150
150
150
Maximum Refrigerant Side Pressure, psig
235
235
235
235
235
235
235
Minimum Chilled Water Flow Rate, gpm
140
160
160
180
180
180
180
Maximum Chilled Water Flow Rate, gpm
675
750
750
800
800
800
800
Water Connections, in.
8
10
10
10
10
10
10
Contact your nearest Johnson Controls Sales Office for weight data.
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...