JOHNSON CONTROLS
130
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
Models YCIV0357E/V and YCIV0397S/P/H
DIMENSIONS - 2 & 3 COMPRESSOR ENGLISH (CONT'D)
VIEW C-C
VIEW B-B
12"
CONTROL ENTRY
3" WIDE X 13 1/2" HIGH
1 1/2"
4"
POWER ENTRY
10" WIDE X 13" HIGH
1 3/4"
POWER ENTRY IS ON BOTTOM OF PANEL
88 1/8"
C
B
B
C
VIEW A-A
POWER ENTRY
10" WIDE X 13"
HIGH
Placement on a level surface of free of
obstructions (including snow, for winter
operation) or air circulation ensures rated
performance, reliable operation, and ease
of maintenance. Site restrictions may
compromise minimum clearances indi-
cated below, resulting in unpredictable
airflow patterns and possible diminished
performance.
Johnson Controls unit controls will op-
timize operation without nuisance high-
pressure safety cutouts; however, the
system designer must consider potential
performance degradation. Access to the
unit control center assumes the unit is no
higher than on spring isolators. Recom-
mended minimum clearances: side to wall
– 2 m; rear to wall – 2 m; control panel to
end wall – 1.2 m; top – no obstructions
whatsoever; distance between adjacent
units – 3 m. No more than one adjacent
wall may be higher than the unit.
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...