JOHNSON CONTROLS
272
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
A sample of the operating data printout is shown be-
low. The operating data printout is a snapshot of cur-
rent system operating conditions when the printout was
selected. The sample shows combined printouts of 2, 3,
and 4 circuit units. The actual printout will only show
data for the appropriate chiller type.
Bold italic text below a line of print is not
on the actual printout. Bold italic text
indicates information that may not be
available on all printouts or is additional
information to help explain the difference
in a 2/3 or 4-circuit printout.
Operating Data Printout
YORK INTERNATIONAL CORPORATION
LATITUDE SCREW CHILLER
OPERATING DATA
2:04:14 PM 18 FEB 10
SYS 1
NOT RUNNING
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED
LIQUID
WATER
LOCAL/REMOTE
MODE
REMOTE
LEAD/LAG
CONTROL
AUTOMATIC
REMOTE TEMP RESET
DISABLED
REMOTE CURRENT LIMIT
0 TO 10 V
REMOTE SOUND LIMIT
4 TO 20 MA
(if Sound Limiting enabled)
LOW AMBIENT CUTOUT
ENABLED
PROGRAM VALUES
SUCT PRESS CUTOUT
44 PSIG
LOW AMBIENT CUTOUT
25.0 DEGF
LEAVING LIQUID CUTOUT
36.0 DEGF
MOTOR CURRENT LIMIT
100 %FLA
PULLDOWN CURRENT LIMIT
100 %FLA
PULLDOWN LIMIT TIME
0 MIN
SUCTION SUPERHEAT SETP
12.0 DEGF
UNIT ID NUMBER
0
SOUND LIMIT SETPOINT
100%
(if Sound Limiting enabled)
UNIT DATA
LEAVING LIQUID TEMP
49.0 DEGF
RETURN LIQUID TEMP
58.2 DEGF
TEMP RATE
XXX.X DEGF/MIN
COOLING RANGE
42.0+/-2.0 DEGF
REMOTE SETPOINT
44.0 DEGF
AMBIENT AIR TEMP
74.8 DEGF
LEAD
SYSTEM
SYS
2
FLOW
SWITCH
ON
EVAPORATOR PUMP RUN
ON
EVAPORATOR
HEATER
OFF
ACTIVE REMOTE CONTROL
NONE
OPERATING HOURS 1=XXXXX, 2=XXXXX
3=XXXXX
(3 circuit)
3=XXXXX,
4=XXXXX
START COUNTER
1=XXXXX, 2=XXXXX
3=XXXXX
(3 circuit)
3=XXXXX,
4=XXXXX
(4 circuit)
SOFTWARE VERSION
C.ACS.XX.00
VSD DATA
ACTUAL FREQUENCY
XXX.X HZ
COMMAND FREQUENCY
XXX.X HZ
DC BUS VOLTAGE
XXX VDC
(2 circuit & 3 circuit)
DC BUS VOLTAGES
XXX XXX VDC
(4 circuit)
INTERNAL AMBIENT TEMP XXX.X DEGF
COOLING SYSTEM STATUS XXX
BASEPLATE TEMPS
XXX XXX DEGF
PRECHARGE SIGNAL
XXX
(2 circuit & 3 circuit)
PRECHARGE SIGNALS
XXX XXX
(4 circuit)
MOTOR OVERLOADS 1/2
XXX XXX AMPS
MOTOR OVERLOADS 3/4
XXX XXX AMPS
(3 circuit & 4 circuit)
SOFTWARE VERSION
C.VSD.XX.00
SYSTEM 1 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
0AMPS 0 %FLA
SUCTION PRESSURE
125 PSIG
DISCHARGE PRESSURE
131 PSIG
OIL PRESSURE
130 PSIG
SUCTION TEMPERATURE
68.4 DEGF
DISCHARGE TEMPERATURE 68.8 DEGF
OIL TEMPERATURE
68.8 DEGF
SAT SUCTION TEMP
71.8 DEGF
SUCTION SUPERHEAT
3.4 DEGF
SAT DISCHARGE TEMP
74.5 DEGF
DISCHARGE SUPERHEAT
6.3 DEGF
MOTOR TMP XXX.X XXX.X XXX.X DEGF
COMPRESSOR SPEED
XXX.X %
ECONOMIZER SOLENOID
OFF
FLASH TANK LEVEL
XXX.X %
FEED VALVE % OPEN
XXX.X %
DRAIN VALVE % OPEN
XXX.X %
CONDENSER FANS ON
0
COMPRESSOR HEATER
ON
RUN PERMISSIVE
ON
VSD RUN RELAY
OFF
VSD SOFTWARE RUN SIGNAL OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
RUN TIME
0-0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS
87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
218 PSIG
SUCTION TEMPERATURE
42.9 DEGF
DISCHARGE TEMPERATURE
145.5 DEGF
OIL
TEMPERATURE
102.8
DEGF
SAT SUCTION TEMP
31.7 DEGF
SUCTION SUPERHEAT
11.2 DEGF
SAT DISCHARGE TEMP
112.1 DEGF
DISCHARGE SUPERHEAT
33.4 DEGF
MOTOR TMP
XXX.X XXX.X XXX.X
DEGF
COMPRESSOR
SPEED
XXX.X%
LIQUID LINE SOLENOID
ON
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...