JOHNSON CONTROLS
285
SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
TABLE 25 -
ANALOG INPUT CONNECTIONS
BOARD
HEADER
ANALOG INPUT
Chiller Control Board
J17-11
Remote Temperature Reset
Chiller Control Board
J17-12
Remote Current Limit
Chiller Control Board
J17-13
Spare 1
Chiller Control Board
J17-14
Spare 2
Chiller Control Board
J17-15
Spare 3
Chiller Control Board
J8-7
Leaving Chilled Liquid Temp Sensor
Chiller Control Board
J8-8
Return Chilled Liquid Temp Sensor
Chiller Control Board
J8-9
Ambient Air Temp Sensor
Chiller Control Board
J19-1
Comp 1 Motor Temperature 1
Chiller Control Board
J19-2
Comp 1 Motor Temperature 2
Chiller Control Board
J19-3
Comp 1 Motor Temperature 3
Chiller Control Board
J19-6
Comp 2 Motor Temperature 1
Chiller Control Board
J19-7
Comp 2 Motor Temperature 2
Chiller Control Board
J19-8
Comp 2 Motor Temperature 3
Chiller Control Board
J21-13
Sys 1 Suction Temperature
Chiller Control Board
J21-3
Sys 1 Oil Temperature
Chiller Control Board
J21-16
Sys 1 Discharge Temperature
Chiller Control Board
J21-6
Sys 1 Flash Tank Level Sensor
Chiller Control Board
J21-20
Sys 1 Suction Pressure
Chiller Control Board
J21-22
Sys 1 Oil Pressure
Chiller Control Board
J21-24
Sys 1 Discharge Pressure
Chiller Control Board
J22-13
Sys 2 Suction Temperature
Chiller Control Board
J22-2
Sys 2 Oil Temperature
Chiller Control Board
J22-16
Sys 2 Discharge Temperature
Chiller Control Board
J22-6
Sys 2 Flash Tank Level Sensor
Chiller Control Board
J22-20
Sys 2 Suction Pressure
Chiller Control Board
J22-22
Sys 2 Oil Pressure
Chiller Control Board
J22-24
Sys 2 Discharge Pressure
Chiller Control Board
J20-1
Comp 3 Motor Temperature 1
TABLE 24 -
SERIAL PORT CONNECTIONS
BOARD
HEADER
PORT TYPE
PORT USE
Chiller Control Board
TB1 / TB2
RS-232 / RS-485
Printer/RCC and ISN
Chiller Control Board
J2 / J1
RS-485
Control Panel <-> VSD #1 / #2
VSD Logic Board
J12
Opto- Coupled RS-485
VSD <-> Control Panel
ANALOG INPUT CONNECTIONS
lists the Analog inputs and the
circuit board they are located on. Not all of the sen-
sors are installed in every unit, as some of them are
optional. The software must read the optional sensors
if installed. The Analog input signals are typically ref-
erenced to the common (return, ground) in the system.
J12-3 can also be used as common, as well as chassis
ground, or the common terminal point on the Chiller
Control Board. See the wiring diagrams. The +DC
Bus, -DC Bus and ½ DC Bus voltages are measured
in reference to one of the other DC Bus points. For
example: +DC Bus measured to ½ DC Bus.
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...