SECTION 8 - MICROPANEL
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
8
Sensor Displays
lists all the sensors attached
to the control board associated with system data keys.
The minimum and maximum values displayed on the
micro display are provided.
If values exceed the limits in the table, a < (less than)
or > (more than) sign will be display along with the
minimum or maximum value.
TABLE 19 -
SENSOR MIN/MAX OUTPUTS
SENSOR
TYPE
MINIMUM
MAXIMUM
Suction
Pressure
Transducer
0.0 psig
125.0 psig
Oil
Pressure
Transducer
0.0 psig
275.0 psig
Discharge
Pressure
Transducer
0.0 psig
275.0 psig
Flash Tank
Level
Capacitance
0.0%
100 %
Leaving Chilled
Liquid Temp.
3Kohm
Thermistor
-19.1ºF
110.2ºF
Return Chilled
Liquid Temp.
3Kohm
Thermistor
-19.1ºF
110.2ºF
Ambient Air
Temp.
10Kohm
Thermistor
-4.6ºF
137.9ºF
Suction
Temp.
3Kohm
Thermistor
-4.1ºF
132.8ºF
Oil Temp.
50Kohm
Thermistor
40.3ºF
302.6ºF
Discharge
Temp.
50Kohm
Thermistor
40.3ºF
302.6ºF
Compressor
Motor Temp.
10Kohm
Thermistor
-30.0ºF
302.0ºF
Remote Temp.
Reset
4–20 mA / 2–10 VDC
0%
100%
0–20 mA / 0–10 VDC
Remote
Current Limit
4–20 mA / 2–10 VDC
0%
100%
0–20 mA / 0–10 VDC
Remote
Sound Limit
4–20 mA / 2–10 VDC
0%
100%
0–20 mA / 0–10 VDC
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...