JOHNSON CONTROLS
78
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
HIGH EFFICIENCY 3-COMPRESSOR UNITS
(One Field Provided Power Supply Circuit. Field Connections to Factory provided
Terminal Block (Standard); or Individual System Breakers (Optional).
MODEL NO./NAME-
PLATE
SYSTEM 1
SYSTEM 2
SYSTEM 2
SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC
COND. FANS
TWO-SPEED COND.
FANS
YCIV
E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
COMP. CONDENSER
FANS
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
RLA
(5)
QTY.
FLA
(EA)
0267
460
60
142
5
2.8
142
5
2.8
105
4
2.8
380
60
179
5
3.5
179
5
9.3
179
4
3.5
179
4
9.3
133
4
3.5
133
4
9.3
0287
460
60
137
5
2.8
137
5
2.8
137
5
2.8
380
60
173
5
3.5
173
5
9.3
173
5
3.5
173
5
9.3
173
4
3.5
173
4
9.3
0327
460
60
152
5
2.8
152
5
2.8
141
6
2.8
380
60
193
5
3.5
193
5
9.3
193
5
3.5
193
5
9.3
178
6
3.5
178
6
9.3
0357
460
60
181
6
2.8
181
6
2.8
139
6
2.8
380
60
229
6
3.5
229
6
9.3
229
6
3.5
229
6
9.3
176
6
3.5
176
6
9.3
YCIV
S/P/H
Control
KVA (7)
Unit Short Circuit
Withstand (KA)
Field Wiring & Protection
Field Wiring & Protection
Field Wiring Lugs
Std. & Ultra Quiet Cond. Fans
High Head/High Static Fans
High Head/High Static
Fans
Two-Speed Cond. Fans
STD Terminal
Block
OPT Circuit
Breaker
Terminal
Block
(STD)
Circuit
Breaker
(OPT)
Mini-
mum Ckt.
Ampacity
(MCA) (3)
Recommend-
ed Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Minimum
Ckt.
Ampacity
(MCA) (3)
Recommended
Fuse/Ckt.
Breaker
Rating (4)
Max.
Inverse
Time Ckt.
Brkr. Rat-
ing (2)
Max Dual
Element
Fuse
Size (2)
Lugs/
Phase
(1)
Lug Wire
Range
Lugs/
Phase
(1)
Lug Wire
Range
0287
2.4
30
65
463
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30
65
581
700
700
700
632
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0307
2.4
30
65
486
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30
65
610
700
700
700
659
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0357
2.4
30
65
528
600
600
600
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30
65
667
800
800
800
728
800
800
800
4
#2 - 600
KCM
4
#4/0 - 500
KCM
0397
2.4
30
65
598
700
700
700
4
#2 - 600
KCM
4
#4/0 - 500
KCM
2.4
30
65
755
800
800
800
818
1000
1000
1000
4
#2 - 600
KCM
4
#4/0 - 500
KCM
See page 92 for Electrical Data footnotes.
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...