JOHNSON CONTROLS
274
FORM 201.23-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - MICROPANEL
LD10605
SERVICE
KEY
SERVICE KEY
Service Key Operation
The SERVICE key allows viewing data related to the
internal function of the chiller system electronics. Data
such as circuit board output status as controlled by the
Chiller Control software while operating can be viewed
and compared to actual chiller operation in the event
servicing is required. The SERVICE key allows con-
trolling of analog and digital outputs for troubleshoot-
ing purposes when the unit is not running. The Unit
Serial Number and Optimized IPLV Control mode are
also entered using the SERVICE key.
The
▲▼
(ARROW) keys allow scrolling through the
displays. The
▼
(ARROW) key scrolls through the
displays in the forward direction.
When the SERVICE key is pressed, the following mes-
sage will appear:
SERVICE MODE XXXX
PRESS ENTER KEY TO CONTINUE
XXXX will display a password, if a numerical pass-
word is entered.
Pressing the
(ENTER) key allows “view only” Ser-
vice Mode operation. All control board I/O will be
viewable in this mode. No outputs can be changed. For
troubleshooting or start-up commissioning purposes,
the Chiller Micro Board and some VSD outputs can be
toggled or changed by turning off the UNIT SWITCH,
pressing the SERVICE key, entering password 9675,
and pressing the
(ENTER) key. Once the password
is entered, the Digital Outputs (DO) can be toggled by
pressing the
(ENTER) key. The Analog Outputs can
be programmed to output a specific value using the
keypad and programming in the desired value, which
will usually be noted as a % or VDC. If the UNIT
SWITCH is turned back on, the chiller will revert to
normal viewable only control.
Displays can be viewed by pressing the
▲
and
▼
(AR-
ROW) keys. The
▼
(ARROW) key scrolls through the
displays in the forward direction.
The
◄
and
►
(ARROW) keys allow jumping from
data section to data section to avoid scrolling sequen-
tially through all the data. Once in a data section, the
▲
and
▼
(ARROW) keys allow scrolling through the
data under the section. Pressing the
◄
and
►
(AR-
ROW) keys at any time moves to the top of the next
data section.
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...