TABLE 12 -
VSD BASEPLATE TEMPERATURE
LOAD LIMITING/UNLOADING
VSD BASEPLATE TEMPERATURE
UN-LOADING
Baseplate Temp. is between
Cutout- 8ºF & Cutout- 4ºF
0 Hz
Baseplate Temp. Cutout- 3.6ºF
1 Hz
Baseplate Temp. Cutout- 3.2ºF
2 Hz
Baseplate Temp. Cutout- 2.8ºF
3 Hz
Baseplate Temp. Cutout- 2.4ºF
4 Hz
Baseplate Temp. Cutout- 2.0ºF
5 Hz
Baseplate Temp. Cutout- 1.6ºF
6 Hz
Baseplate Temp. Cutout- 1.2ºF
7 Hz
Baseplate Temp. Cutout- 0.8ºF
8 Hz
Baseplate Temp. Cutout- 0.4ºF
9 Hz
Baseplate Temp. Cutout
10 Hz
FLASH TANK DRAIN AND FEED VALVE
CONTROLLER
Valve Controller and Control Algorithm
Operation
The Flash Tank Feed and Drain Valve PI Controller(s)
plays a dual role of supplying drive signals to control
the opening and closing of both the Flash Tank Feed
and Drain Valves. These valves control the liquid level
in the flash tank and the suction superheat of the com-
pressor. The Flash Tank Feed and Drain Valve Con-
troller receive analog signals from the Chiller Control
Board to position the Feed and Drain Valves.
The Chiller Control Board PI (Proportional plus In-
tegral) control algorithm in the Chiller Control Board
software determines the open % for the Drain and Feed
valves. A D/A converter on the Chiller Control Board
converts the 0% to 110.0% signal to an output voltage
between 0 VDC and 10.28 VDC and sends it to the
Drain and Feed Controller. This voltage is then con-
verted to a valve position by the Drain and Feed Valve
Controller and a 2 phase (4 wire), signal drives the
Feed Valve open or closed. Power for the Valve Con-
troller comes from a 30 VDC supply from the Chiller
Control Board.
FIGURE 53 -
FLASH TANK DRAIN AND FEED VALVE CONTROLLER
LD10619
Содержание YCIV Series
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...