5
-60
Prohibiting Overwriting of Parameters
If A1-01 is set to 0, all parameters except A1-01 and A1-04 are write protected, U1-
, U2-
and
U3-
will be displayed. If A1-01 is set to 1, only the parameters A1-01, A1-04 and A2-
can be read or
written, U1-
, U2-
and U3-
will be displayed. All other parameters will not be displayed.
If you set one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selection) to 1B
(write parameters permitted), parameters can be written from the digital operator when the terminal that has
been set is ON. When the set terminal is OFF, writing parameters other than the frequency reference is prohib-
ited. However, the parameters can be read.
Related Parameters
Setting a Password
When a password is set in A1-05 and if the set values in A1-04 and A1-05 do not match, only the settings of
parameters A1-01 to A1-03, or A2-01 to A2-32 can be modified.
The setting of all parameters except A1-00 can be prohibited using the password function in combination with
setting parameter A1-01 to 0 (Monitor only).
Related Parameters
Setting a Password
The password can be set in parameter A1-05. Normally A1-05 is not displayed. To display and modify A1-05
the MENU and Reset key must be pressed together in the A1-04 display.
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
Open
Loop
Vector
Closed
Loop
Vector
A1-01
Parameter access level
2
Yes
A
A
A
Parameter
No.
Name
Factory
Setting
Change
during
Opera-
tion
Control Methods
V/f
Open
Loop
Vector
Closed
Loop
Vector
A1-01
Parameter access level
2
No
A
A
A
A1-04
Password
0
No
A
A
A
A1-05
Password setting
0
No
A
A
A