5
-16
Short Floor Operation
Related parameters
Princple
The short floor operation is activated when the leveling signal is set before the nominal speed was reached.
The inverter calculates the distance for deceleration from nominal speed to the levelings speed, which is equal
to the area S in the figure below..
There are two ways:
•
If the leveling speed is set when 40% of the nominal speed was reached already, the inverter keeps the
reached speed until the distance equal to area S is reached. After that it decelerates to leveling speed.
•
If the leveling signal is set before 40% of the nominal speed was reached, the inverter accelerates to 40%
of the nominal speed and keeps it until the distance is equal to area S is reached. After that it decelerates to
leveling speed.
Parameter
No.
Name
Factory
Setting
Change
during
Operation
Control Methods
V/f
Open
Loop
Vector
Closed
Loop
Vector
S3-01
Short floor operation
0
No
A
A
A
Nominal speed
Leveling speed
Leveling speed
Speed
t
S
0
Nominal Speed x 0.4
Speed
t
0
40% Nominal speed
S