4
-58
Factory Settings that Change with the Control Method (A1-02)
* 1. The settings are 0.05 (Closed Loop Vector) / 2.00 (Open Loop vector) for inverters of 55kW or larger.
* 2. Settings value as shown in the following tables depending on the Inverter capacity and E1-03.
* 3. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
Param-
eter
Num-
ber
Name
Setting Range
Unit
Factory Setting
V/f Con-
trol
A1-02=0
Open
Loop
Vector
A1-02=2
Closed
Loop
Vector
A1-02=3
C3-01 Slip compensation gain
0.0 to 2.5
-
1.0
1.0
1.0
C3-02 Slip compensation delay time
0 to 10000
-
2000
200
0
C4-02 Torque compensation delay time constant
0 to 10000
-
200
50
0
E1-07 Mid. output frequency voltage
0.0 to 120.0
0.1 Hz
3.0
3.0
0
E1-08 Mid. output frequency voltage (VB)
*2
0.0 to 255.0
(0.0 to 510.0)
0.1 V
15.0
*2*3
11.0
0.0
E1-09 Min. output frequency (FMIN)
0.0 to 120.0
*4
0.1 Hz
1.5
*2
0.5
0.0
E1-10 Min. output frequency voltage (VMIN)
*2
0.0 to 255.0
(0.0 to 510.0)
0.1 V
9.0
*2*3
2.0
0.0
S1-04 DC injection braking time at stop
0.00 to 10.00
0.01 sec
0.50
0.30
0.00