Timing Charts
Fig 5.14
and
Fig 5.15
show the timing charts for overtorque and undertorque detection.
Fig 5.14 Overtorque Detection
Fig 5.15 Undertorque Detection
Car Stuck Detection (OL3, Using Overtorque detection)
The Overtorque detection function can be used to detect a stucked car. The torque detection function 1 can be
used for this. Therefore a digital output has to be programmed for “Overtorque detection 1” (H2-
= B or
17). Using this with the factory setting car stuck is detected (output is switched) torque/current is higher than
150% for 10 sec. The level can be adjusted in L6-02, the time in L6-03. The output is switched of and an OL3
fault will be indicated (see .
Fig 5.16
)
Fig 5.16 Car Stuck fault detection
Motor current (output torque)
L6-02 or L6-05
L6-03 or
L6-06
L6-03 or
L6-06
Overtorque detection 1 NO
or overtorque detection 2 NO
*Overtorque detection switch off bandwidth is approximately 10% of the Inverter rated output current
(or motor rated torque).
Motor current (output torque)
L6-02 or L6-05
L6-03 or
L6-06
L6-03 or
L6-06
Undertorque detection 1 NO
or ondertorque detection 2 NO
*Undertorque detection switch off bandwidth is approximately 10% of the Inverter rated output
current (or motor rated torque).
Up/Down (D/I)
Selected Speed (D/I)
speed
DC Injection/
zero servo
Fault
Inverter enable (D/I)
detect. time
L6-03
Torque is higher
than L6-02