Digital Operator/Monitor Functions
5-
55
5
Changing the Units for Frequency Parameters Related to V/f settings (o1-04)
Using parameter o1-04 the unit for frequency parameters related to the V/f setting can be changed. If o1-04 is
set to 0 it will be Hz. If o1-04 is set to 1 it will be rpm.
Changing the Display Contrast (o1-05)
Using o1-05 the contrast of the LCD display on the digital operator can be raised or lowered. Lowering the
o1-05 value will decrease the contrast and vice versa.
Disabling the STOP Key (o2-02)
This parameter is used to set whether the STOP key on the operator is active during remote control (b1-02
≠
0)
or not.
If o2-02 is set to 1, a STOP command from the operators STOP key will be accepted. If o2-02 is set to 0 it will
be disregarded.
Initializing Changed Parameter Values (o2-03)
The current Inverter parameter setting values can be saved as user-set parameter initial values. To save there-
fore parameter value o2-03 has to be set to 1.
To initialize the Inverter parameters using the user-set initial values in memory set parameter A1-03 to 1110.
To clear the user-set initial values in memory, set o2-03 to 2.
Changing the Inverter Capacity Setting (o2-04)
The inverter capacity setting can be set using parameter o2-04. Refer to
page 4-60, Factory Settings that
Change with the Inverter Capacity (o2-04)
to see parameters that depend on this setting.
Normally it is not necessary to change this setting, unless the control card has been changed.
Setting the Frequency Reference using the UP and DOWN Keys without Using the
Enter Key (o2-05)
This function is active when frequency references are input from the Digital Operator/Monitor. When o2-05 is
set to 1, the frequency reference. Can be incremented or decremented using the UP and DOWN keys without
using the Enter key.
Operation Selection when the Digital Operator/Monitor is Disconnected (o2-06)
This function selects the inverter operation after disconnected the digital operator when a RUN command is
active.
If o2-06 is set to 0 the operation is continued.
If o2-06 is set to 1 the output is switched off and the motor coasts to stop. The fault contact is operated. When
the operator is reconnected an OPR (Operator disconnected) is shown.
Cumulative Operation Time (o2-07 and o2-08)
The inverter has a function that counts the operation time of the inverter cumulatively.
Using parameter o2-07 the cumulative operation time can be changed, e.g. after a replacement of the control
board. If parameter o2-08 is set to 0 the inverter counts the time whenever the power supply is switched ON.
If o2-08 is set to 1 the time when a RUN command is active is counted only. The factory setting is 0.