Control Sequence
5-
7
5
Separate Speed Selection Inputs, High Speed Has Priority (d1-18=1)
With this setting 6 different speeds can be set and selected using four digital inputs.
Related Parameters
* This speed can be selected by a combination of two inputs
Digital Input Factory Settings
Higher Speed has Priority and a Leveling Speed Input is Selected (H1-
=83)
If d1-18 is set to 1 and one multi-function digital input is set for the leveling speed (H1-
=83) after remov-
ing the selected speed signal the inverter decelerates to the leveling speed (d1-17). The selected speed must be
different from leveling speed and inspection speed. The higher speed has priority over the leveling speed, i.e.
as long as a higher speed is selected the leveling signal is disregarded (see the fig. below)
The inverter stops when the leveling signal or the Forward/Reverse command signal is removed.
The following speed selection table shows the different speeds and the according digital inputs.
When the speed selection which the table is not shown is selected, the inverter keeps running the previous
speed reference.
* 0 = disabled, 1 = enabled, X = no meaning
Parameter
No.
Name
Factory
Setting
Change
during
Operation
Control Methods
Digital Input
Setting (H1-01 to
H1-05)
V/f
Open
Loop
Vector
Closed
Loop
Vector
d1-09
Nominal Speed
50.00 Hz
Yes
Q
Q
Q
80
d1-10
Intermediate Speed 1
0.00 Hz
Yes
A
A
A
81
d1-11
Intermediate Speed 2
0.00 Hz
Yes
A
A
A
-*
d1-12
Intermediate Speed 3
0.00 Hz
Yes
A
A
A
-*
d1-13
Releveling Speed
0.00 Hz
Yes
A
A
A
82
d1-17
Leveling Speed
4.00 Hz
Yes
Q
Q
Q
83
Terminal
Parameter
Number
Set Value
Details
S3
H1-01
24
External Fault
S4
H1-02
14
Fault Reset
S5
H1-03
3
Multi-step speed command1
S6
H1-04
4
Multi-step speed command2
S7
H1-05
6
JOG reference
Terminal function
Nominal
Speed
d1-09
Intermed.
Speed 1
d1-10
Intermed.
Speed 2
d1-11
Intermed.
Speed 3
d1-12
Relevel.
Speed
d1-13
Leveling
Speed
d1-17
0Hz
Nominal Speed command (H1-
=80)
1
0
1
0
0
0
0
Intermediate speed command (H1-
=81)
0
1
1
1
0
0
0
Releveling speed command (H1-
=82)
0
0
1
1
1
0
0
Leveling speed command (H1-
=83)
X
X
X
X
X
1
0
Up/Donw
Leveling speed
Selected speed
Speed
DC Injection/
zero servo
DC Injection/
zero servo
Input is set
No effect
Hardware BB
Leveling speed
http://nicontrols.com