Setting User Constants
4.2.4 Operation Mode
4 - 12
J
Conditions for Monitoring
Table 4.3 shows the items that can be monitored in operation mode.
The “Valid access levels” column in the table indicates whether an item can be monitored in a particular
access level and control method. The codes in this column have the following meanings.
Q
Items that can be monitored in all access levels. (Quick-start, Basic, and Advanced)
B
Items that can be monitored in the Advanced and Basic access levels.
A
Items that can be monitored only in the Advanced access level.
×
Items that cannot be monitored in the control mode shown.
The output signal levels for multi-function analog outputs shown in the table are for a gain of 100.0 and
a bias of 0.00.
Table
4.3
Constants Monitored in Operation Mode
Con
Name
Output Signal Levels for
Valid Access Levels
Func-
tion
Con-
stant
No.
Digital Operator
Display
Function
Output Signal Levels for
Multi-function Analog Out-
puts
Min.
Unit
V/f
V/f w/
PG
Open
-loop
Vec-
tor
Flux
Vec-
tor
U1-01
Frequency refer-
ence
Monitors/sets the frequency ref-
erence value.
Th di l
it
b
t ith
10 V: Max. frequency
(0 t
10 V
ibl )
0
.
01
Hz
Q
Q
Q
Q
U1 01
Frequency Ref
The display units can be set with
user constant o1-03.
(0 to
±
10 V possible)
Hz
Q
Q
Q
Q
U1 02
Output frequency
Monitors the output frequency.
Th di l
it
b
t ith
10 V: Max. frequency
0
.
01
Q
Q
Q
Q
U1-02
Output Freq
The display units can be set with
user constant o1-03.
10 V: Max. frequency
(0 to
±
10 V possible)
0
.
01
Hz
Q
Q
Q
Q
U1 03
Output current
Monitors the output current
10 V: Rated current
0 1 A
Q
Q
Q
Q
U1-03
Output Current
Monitors the output current.
10 V: Rated current
(0 to +10 V output)
0
.
1 A
Q
Q
Q
Q
U1 04
Control method
Shows which control mode is
Can’t be output
Q
Q
Q
Q
U1-04
Control Method
Shows which control mode is
set.
Can’t be output.
−−
Q
Q
Q
Q
U1 05
Motor speed
Monitors the motor speed.
Th di l
it tti
b
10 V: Max. frequency
0
.
01
×
Q
Q
Q
U1-05
Motor Speed
The display unit setting can be
changed using o1-03.
10 V: Max. frequency
(0 to
±
10 V possible)
0
.
01
Hz
×
Q
Q
Q
U1 06
Output voltage
Monitors the Inverter’s internal
10 V: 200 (400) VAC
0 1 V
Q
Q
Q
Q
U1-06
Output Voltage
Monitors the Inverter s internal
output voltage reference value.
10 V: 200 (400) VAC
(0 to +10 V output)
0
.
1 V
Q
Q
Q
Q
U1 07
DC bus voltage
Monitors the DC voltage of the
10 V: 400 (800) VDC
1 V
Q
Q
Q
Q
S
U1-07
DC Bus Voltage
Monitors the DC voltage of the
Inverter’s internal main circuit.
10 V: 400 (800) VDC
(0 to +10 V output)
1 V
Q
Q
Q
Q
Status
Moni-
U1 08
Output power
Monitors the output power.
(This is an internally detected
10 V: Max. motor capacity
0 1 kW
Q
Q
Q
Q
Moni-
tor
U1-08
Output kWatts
(This is an internally detected
value.)
10 V: Max. motor capacity
(0 to
±
10 V possible)
0
.
1 kW
Q
Q
Q
Q
U1 09
Torque reference
Monitors the internal torque ref-
erence value when vector con
10 V: Rated torque
0 1 %
×
×
Q
Q
U1-09
Torque Reference
erence value when vector con-
trol is used.
10 V: Rated torque
(0 to
±
10 V possible)
0
.
1 %
×
×
Q
Q
U1-10
Input terminal sta-
tus
Shows input ON/OFF status.
U1-10 = 0 0 0 0 0 0 0 0
1: Terminal 1 ON
1: Terminal 2 ON
1: Terminal 3 ON
Can’t be output.
−−
Q
Q
Q
Q
U1 10
Input Term Sts
1: Terminal 4 ON
1: Terminal 5 ON
1: Terminal 6 ON
1: Terminal 7 ON
1: Terminal 8 ON
Can t be output.
Q
Q
Q
Q
U1-11
Output terminal
status
Shows output ON/OFF status.
U1-11 = 0 0 0 0 0 0 0 0
1: Terminals 9
−
10 ON
1: Terminal 25 ON
Can’t be output.
−−
Q
Q
Q
Q
U1 11
Output Term Sts
1: Terminal 26 ON
Not used. (always 0)
1: Terminals 18/19
−
20
ON
Can t be output.
Q
Q
Q
Q
4
Содержание VARISPEED-616G5
Страница 1: ......