7.3 Flux Vector Control
7 - 35
D
Settings
Setting
Function
0
Disables limited output voltage operation.
1
Enables limited output voltage operation.
D
If the limited output voltage operation is disabled and output voltage becomes saturated, the output
current does not change. However, torque control precision is no longer possible.
Enable limited output voltage operation if precise torque control is required.
D
If the limited output voltage operation is enabled, the magnetic flux current of the motor is automatical-
ly controlled, and the output voltage command itself is limited, which maintains precise torque control.
Check the Inverter current margins as the output current will be maximum 10% higher (with a rated
load) than when limited output voltage operation is disabled.
Note 1.C3-06 does not need to be changed if the Unit is used only at medium or low speeds, or
when the power supply voltage is 10% or more higher than the rated voltage for the motor,
or when torque control precision in the high-speed region is not required.
2. When the power supply voltage is too low for the rated motor voltage, precise torque con-
trol will not be maintained even if limited output voltage operation is enabled.
7