User Constants
8.2.7 Protection Constants: L
8 - 42
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
L8-19
OL2 characteristics
selection at low
speeds
0: OL2 characteristics at low
speeds disabled.
1: OL2 characteristics at low
speeds enabled.
:
If using OL2 to trip at low
speeds (less than 6 Hz) even
though the load is light, set
L8-17 to 1 and L8-19 to 0
0, 1
0*
×
A
A
A
A
7 - 96
OL2 Chara@ L-Spd
L8-17 to 1 and L8-19 to 0.
However, do not set L8-17 or
L8-19 to 0 when using V/f and
open-loop vector control.
Do not set L8-19 to 0 when us-
ing a 400 V class (185 to 300
kW) Inverter.
* Reduce the carrier frequency selection (C6-01) to 2 kHz when operating continuously at low speeds with