Basic Operation
6.1.1 Setting the Access Level and Control Method: A1-01, A1-02
6 - 2
6.1 Common Settings
This section describes the constants that are used with all of the control methods.
6.1.1 Setting the Access Level and Control Method: A1-01, A1-02
J
Constant Access Level: A1-01
D
Select the constant access level. This level determines which constants can be accessed and changed.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
A1-01
Constant access lev-
el
f
0 to 4
−
2
(Q)
Q
Q
Q
Q
D
Access Level Settings
Setting
Name
Function
0
Operation Only
Allows the operation mode and initialize mode to be displayed or
changed. Use this setting to prevent constant settings from being
changed.
1
User Program
Allows only the user-selected constants (up to 32) to be displayed or
changed. Set the desired constants as “User Parameters” in constants
A2-01 through A2-32.
2
Quick-Start
Allows the constants required to start the Inverter (about 25) to be
displayed or changed.
3
Basic
Allows the commonly used constants to be displayed or changed.
4
Advanced
Allows all constants to be displayed or changed.
D
The control method setting also affects which constants can be displayed and changed. Refer to chapter
8 User Constants.
D
The constants required for basic operation can be displayed and changed in the Basic level, but this
section also describes constants that can be set only in the Advanced level, so set the access level to
Advanced.
Changing the Access Level
The following procedure shows how to change from Quick-Start to Advanced.
Step
Key Sequence
Digital Operator Display
Remarks
1
MENU
G5
:
Main Menu
:
Operation
Displays operation mode.
2
G5
:
Main Menu
:
Initialize
Displays initialize mode.
3
DATA
ENTER
Select Language
English
Puts the Unit in initialize mode.
(Select Language display)
4
Access Level
Quick-Start
Displays the Access Level (A1-01).
5
DATA
ENTER
A1-01 = 2
:::
Quick-Start
Displays the constant setting for
A1-01.
6
Press Twice.
A1-01 = 4
Advanced
Displays Advanced.
7
DATA
ENTER
Entry Accepted
Writes the new setting.
Access Level
Advanced
Returns to the Access Level display.