8.2 Programming Mode Constants
8 - 5
8.2 Programming Mode Constants
8.2.1 Application Constants: b
J
Operation Mode Selections: b1
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
b1 01
Reference selection
Used to set the input method for
the frequency reference.
0: Digital Operator
1: Control circuit terminals (ana-
log inputs).
0 to 4
1
×
Q
Q
Q
Q
6 - 4
b1-01
Reference Source
og puts).
2: MEMOBUS transmission (us-
ing SI-K2)
3: Option Card
4: MEMOBUS transmission (for
CP-717)
0 to 4
1
×
Q
Q
Q
Q
6 4
6 - 7
b1-02
Operation method
selection
Used to set the source of the run
command.
0: Digital Operator
1: Control circuit terminals (se-
quence inputs).
2 MEMOBUS t
i i
(
0 to 4
1
×
Q
Q
Q
Q
6 - 9
b1 02
Run Source
2: MEMOBUS transmission (us-
ing SI-K2)
3: Option Card
4: MEMOBUS transmission (for
CP-717)
0 to 4
1
×
Q
Q
Q
Q
6 9
b1-03
Stopping method
selection
Used to set the stopping method
used when a stop command is in-
put.
0: Ramp to stop
1: Coast to stop.
2: DC injection braking stop:
(Stops faster than coast to
t
ti
0 to 3
0
×
Q
Q
Q
Q
6 - 12
b1 03
Stopping Method
(
p
stop, no regenerative opera-
tion.)
3: Coast to stop with timer: Run
commands are disregarded
during deceleration.
:
Only settings 0 and 1 can be
used with flux vector control.
0 to 3
0
×
Q
Q
Q
Q
6 12
b1-04
Prohibition of reverse
operation
0: Reverse enabled
1 R
di bl d
0, 1
0
×
B
B
B
B
6 - 11
b1 04
Reverse Oper
1: Reverse disabled
0, 1
0
×
B
B
B
B
6 11
b1-05
Operation selection
for setting of E1-09 or
less
Used to set the method of opera-
tion when the frequency reference
input is less than the minimum
output frequency (E1-09).
0: Run at frequency reference
(E1-09 not effective).
1: STOP (Frequencies below
E1-09 in the coast to stop
state )
0 to 3
0
×
×
×
×
A
6 - 31
Zero-Speed Oper
state.)
2: Run at min. frequency.
(E1-09)
3: Run at zero speed (Frequen-
cies below E1-09 are zero)
:
This function is only available
in with flux vector control.
8
Содержание VARISPEED-616G5
Страница 1: ......