Basic Operation
6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09
6 - 8
Setting
Function
2 to 39
r/min units
r/min = 120
×
frequency reference (Hz)/o1-03
(o1-03 becomes the motor pole)
40 to 39999
Set the binary point position using the value of the fifth digit of o1-03.
The display when the fifth digit = 0 will be
VVVV
The display when the fifth digit = 1 will be
VVV
.
V
The display when the fifth digit = 2 will be
VV
.
VV
The display when the fifth digit = 3 will be
V
.
VVV
Set the values for 100% frequency for the fourth to first digits of o1-03.
Example 1
Set o1-03=12000 when 100% speed is set to 200.0.
100% speed will be displayed as 200.0 when o1-03 is set to 12000.
60% speed will be displayed as 120.0.
Example 2
Set o1-03=26500 when 100% speed is set to 65.00.
60% speed will be displayed as 39.00 when o1-03 is set to 26500.
D
When the 40 to 39,999 range is used, any unit can be set for the reference frequency.
For example, the frequency reference can be displayed or set in units such as mm/s or m/min to coin-
cide with the linear operating speed of the machine.
J
Preset Frequency Reference Values: d1-01 through d1-09
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
d1-01
Frequency refer-
ence 1
f
0 to 400.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-02
Frequency refer-
ence 2
f
0 to 400.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-03
Frequency refer-
ence 3
f
0 to 400.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-04
Frequency refer-
ence 4
f
0 to 400.00
o1-03 0.00 Hz
Q
Q
Q
Q
d1-05
Frequency refer-
ence 5
f
0 to 400.00
o1-03 0.00 Hz
B
B
B
B
d1-06
Frequency refer-
ence 6
f
0 to 400.00
o1-03 0.00 Hz
B
B
B
B
d1-07
Frequency refer-
ence 7
f
0 to 400.00
o1-03 0.00 Hz
B
B
B
B
d1-08
Frequency refer-
ence 8
f
0 to 400.00
o1-03 0.00 Hz
B
B
B
B
d1-09
Jog frequency ref-
erence
f
0 to 400.00
o1-03 6.00 Hz
Q
Q
Q
Q
D
The units for these values are set in o1-03.
D
The frequency reference default value and set value will change when o1-03 is changed.
For example, if preset reference 1 is set to 6.00 Hz and o1-03 is changed to 1 (0.01% units), the setting
for preset reference 1 will become 10.00%.
D
When using preset references 2 through 8, be sure to set multi-step speed references 1, 2, and 3 in the
multi-function inputs (H1-01 through H1-06) as required.
D
When using the jog function, set the jog frequency reference in constant d1-09. When jogging from
an external terminal, set the multi-function inputs (H1-01 through H1-06) to “Jog Frequency Refer-
ence,” “Forward Jog,” or “Reverse Jog” as required.
D
The multi-function input setting is unnecessary when jogging from the Operator.