8.2 Programming Mode Constants
8 - 45
8.2.9 Factory Settings that Change with the Control Method (A1-02)
Con
Name
Factory Setting
Con-
stant
Num-
ber
Display
Setting
Range
Unit
V/f Con-
trol
A1-02=0
V/f with
PG
A1-02=1
Open
Loop
Vector
A1-02=2
Flux Vec-
tor
A1-02=3
b3 01
Speed search selection at start
0 1
1
0
1
0
1
b3-01
SpfSrch at Start
0, 1
1
0
1
0
1
b3 02
Speed search operating current
0 to 200
1%
150
100
b3-02
SpdSrch Current
0 to 200
1%
150
−−
100
−−
C3 01
Slip compensation gain
0 0 to 2 5
0 1
0 0
1 0
1 0
C3-01
Slip Comp gain
0.0 to 2.5
0.1
0.0
−−
1.0
1.0
C3 02
Slip compensation primary delay time
0 to 10000
1 msec
2000
200
C3-02
Slip Comp Time
0 to 10000
1 msec
2000
−−
200
−−
C4 02
Torque compensation time constant
0 to 10000
1 msec
200 *
3
200 *
3
20
C4-02
Torq Comp Time
0 to 10000
1 msec
200 *
3
200 *
3
20
−−
C5 01
ASR proportional (P) gain 1
0 00 to 300 00
0 01
0 20
20 00
C5-01
ASR P Gain 1
0.00 to 300.00
0.01
−−
0.20
−−
20.00
C5 02
ASR integral (I) time 1
0.000 to
0 001 sec
0 200
0 500
C5-02
ASR I Time 1
0.000 to
10.000
0.001 sec
−−
0.200
−−
0.500
C5 03
ASR proportional (P) gain 2
0 00 to 300 00
0 01
0 02
20 00
C5-03
ASR P Gain 2
0.00 to 300.00
0.01
−−
0.02
−−
20.00
C5 04
ASR integral (I) time 2
0.000 to
0 001 sec
0 050
0 500
C5-04
ASR I Time 2
0.000 to
10.000
0.001 sec
−−
0.050
−−
0.500
E1-04 Max. output frequency
0 0 to 400 0
0 1 Hz
60 0 *
2
60 0 *
2
60 0
60 0
E1 04
E4-01 Max Frequency
0.0 to 400.0
0.1 Hz
60.0 *
2
60.0 *
2
60.0
60.0
E1-05 Max. voltage
0 0 to 255 0
0 1 V
200 0 *
2
200 0 *
2
200 0
200 0
E1 05
E4-02 Max Voltage
0.0 to 255.0
0.1 V
200.0 *
2
200.0 *
2
200.0
200.0
E1-06 Max. voltage frequency
0 0 to 400 0
0 1 Hz
60 0 *
2
60 0 *
2
60 0
60 0
E1 06
E4-03 Max Voltage Frequency
0.0 to 400.0
0.1 Hz
60.0 *
2
60.0 *
2
60.0
60.0
E1-07 Mid. output frequency
0 0 to 400 0
0 1 Hz
3 0 *
2
3 0 *
2
3 0
E1 07
E4-04 Mid Frequency A
0.0 to 400.0
0.1 Hz
3.0 *
2
3.0 *
2
3.0
---
E1-08 Mid. output frequency voltage *
1
0.0 to 255.0
0 1 V
15 0 *
2
15 0 *
2
11 0
E1 08
E4-05 Mid voltage A
0.0 to 255.0
(0.0 to 510.0)
0.1 V
15.0 *
2
15.0 *
2
11.0
---
E1-09 Min. output frequency
0 0 to 400 0
0 1 Hz
1 5 *
2
1 5 *
2
0 5
0 0
E1 09
E4-06 Min Frequency
0.0 to 400.0
0.1 Hz
1.5 *
2
1.5 *
2
0.5
0.0
E1-10 Min. output frequency voltage *
1
0.0 to 255.0
0 1 V
9 0 *
2
9 0 *
2
2 0
E1 10
E4-07 Min Voltage
0.0 to 255.0
(0.0 to 510.0)
0.1 V
9.0 *
2
9.0 *
2
2.0
---
F1 09
Overspeed detection delay time
0 0 to 2 0
0 1 sec
1 0
0 0
F1-09
PG Overspd Time
0.0 to 2.0
0.1 sec
−−
1.0
−−
0.0
* 1. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.
* 2. Settings vary as shown in the following tables depending on the Inverter capacity and V/F pattern selection (E1-03).
* 3. The setting will be 1000 msec for 200 V class inverters of 30 kW or larger, or 400 V class inverters of 55 kW or larger.
8