8.2 Programming Mode Constants
8 - 31
J
Analog Inputs: H3
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H3-01
Signal level selection
(terminal 13)
0: 0 to + 10V [11-bit + polarity
(positive/negative) input]
0, 1
0
×
B
B
B
B
6 - 4
H3 01
Term 13 Signal
(positive/negative) input]
1: 0 to
±
10V
0, 1
0
×
B
B
B
B
6 4
H3 02
Gain (terminal 13)
Sets the frequency when 10 V is
input as a percentage of the maxi
0.0 to
100 0
f
B
B
B
B
6 7
H3-02
Terminal 13 Gain
input, as a percentage of the maxi-
mum output frequency.
0.0 to
1000.0
100.0
f
B
B
B
B
6 - 7
H3 03
Bias (terminal 13)
Sets the frequency when 0 V is in-
put as a percentage of the maxi
−
100.0
to
0 0
f
B
B
B
B
6 7
H3-03
Terminal 13 Bias
put, as a percentage of the maxi-
mum frequency.
to
+ 100.0
0.0
f
B
B
B
B
6 - 7
H3-04
Signal level selection
(terminal 16)
0: 0 to + 10V [11-bit + polarity
(positive/negative) input]
0, 1
0
×
B
B
B
B
6 - 7
H3 04
Term 16 Signal
(positive/negative) input]
1: 0 to
±
10V
0, 1
0
×
B
B
B
B
6 7
H3-05
Multi-function analog
input (terminal 16)
Select from the functions listed in
the following table. Refer to page
0 to 1F
0
×
B
B
B
B
7 - 79
H3 05
Terminal 16 Sel
the following table. Refer to page
7 - 79.
0 to 1F
0
×
B
B
B
B
7 79
H3 06
Gain (terminal 16)
Sets the input gain (level) when
terminal 16 is 10 V.
0.0 to
100 0
f
B
B
B
B
6 7
H3-06
Terminal 16 Gain
terminal 16 is 10 V.
Set according to the 100% value
on page 7 - 79.
0.0 to
1000.0
100.0
f
B
B
B
B
6 - 7
H3 07
Bias (terminal 16)
Sets the input gain (level) when
terminal 16 is 0 V.
−
100.0
to
0 0
f
B
B
B
B
6 7
H3-07
Terminal 16 Bias
terminal 16 is 0 V.
Set according to the 100% value
on page 7 - 79
to
+ 100.0
0.0
f
B
B
B
B
6 - 7
H3-08
Signal level selection
(terminal 14)
0: 0 to +10 V (Always cut jump-
er wire J1)
1: 0 to
±
10 V (Always cut jump-
0 to 2
2
×
A
A
A
A
6 - 4
H3 08
Term 14 Sel
1: 0 to
±
10 V (Always cut jump-
er wire J1)
2: 4 to 20 mA (10-bit input)
0 to 2
2
×
A
A
A
A
6 4
H3-09
Multi-function analog
input (terminal 14)
Set as for H3-05.
:
Cannot be set to 0. The 1F func-
ti
ill b
“f
1 to 1F
1F
×
A
A
A
A
7 - 79
H3 09
Terminal 14 Sel
tion will become “frequency
reference.”
1 to 1F
1F
×
A
A
A
A
7 79
H3 10
Gain (terminal 14)
Sets the input gain (level) when
terminal 14 is 10 V (20 mA).
Set according to the 100% value
0.0 to
100 0
f
A
A
A
A
6 7
H3-10
Terminal 14 Gain
Set according to the 100% value
on page 7 - 79.
If H3-09 = “1F” the setting in
H3-02 is used.
0.0 to
1000.0
100.0
f
A
A
A
A
6 - 7
H3 11
Bias (terminal 14)
Sets the input gain (level) when
terminal 14 is 0 V (4 mA).
Set according to the 100% value
−
100.0
to
0 0
f
A
A
A
A
6 7
H3-11
Terminal 14 Bias
Set according to the 100% value
on page 7 - 79.
If H3-09 = “1F” the setting in
H3-03 is used.
to
+ 100.0
0.0
f
A
A
A
A
6 - 7
H3-12
Analog input filter
time constant
Sets terminals 13, 14, 16 to prima-
ry delay filter time constant, in se-
conds units
0.00 to
2 00
0.00
×
A
A
A
A
6 - 7
H3 12
Filter Avg Time
conds units.
:
Effective for noise control etc.
2.00
0.00
×
A
A
A
A
6 7
8