13.4 Utility Function (Fn
) Operations on the Panel Operator
13.4.5 Initialize Parameters (Fn005)
13-16
13.4.5
Initialize Parameters (Fn005)
Refer to the following section for information on this utility function other than the procedure.
5.1.5 Initializing Parameter Settings
13.4.6
Clear Alarm History (Fn006)
Refer to the following section for information on this utility function other than the procedure.
12.2.5 Clearing the Alarm History
Step
Panel Display after
Operation
Keys
Operation
1
Press the
MODE/SET
Key to enter Utility Function
Mode.
2
Press the
UP
Key or
DOWN
Key to display
Fn005
.
3
Press the
DATA/SHIFT
Key for approximately one sec-
ond. The display shown at the left will appear.
4
Press the
MODE/SET
Key to initialize the parameters.
When the initialization has been completed,
donE
will
flash on the display, and then the display shown on the
left will appear again.
5
To enable the change to the setting, turn the power supply to the SERVOPACK OFF and ON again
after the initialization of the parameter settings has been completed.
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
Step
Panel Display after
Operation
Keys
Operation
1
Press the
MODE/SET
Key to enter Utility Function
Mode.
2
Press the
UP
Key or
DOWN
Key to display
Fn006
.
3
Press the
DATA/SHIFT
Key for approximately one sec-
ond. The display shown at the left will appear.
4
Press the
MODE/SET
Key to clear the alarm history.
When deleting the alarms has been completed,
donE
will flash on the display, and then the display shown on
the left will appear again.
5
Press the
DATA/SHIFT
Key for approximately one sec-
ond to return the display to
Fn006
.
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/
MODE/SET
DATA/