6.6 Position Control
6.6.3 Reference Pulse Input Multiplication Switching
6-34
6.6.3
Reference Pulse Input Multiplication Switching
You can switch the input multiplier for the position reference pulses with the /PSEL (Reference
Pulse Input Multiplication Switch) signal. The number of reference pulses input to the SERVO-
PACK is multiplied by the reference pulse input multiplier. You can change the multiplier from 1
to a specified value n (n can be up to 100). You set the multiplier in Pn218 (Reference Pulse
Input Multiplier).
You can confirm if the multiplier was changed with the /PSELA (Reference Pulse Input Multipli-
cation Switching Output) signal.
This section describes the /PSEL (Reference Pulse Input Multiplication Switch) signal, the refer-
ence pulse input multiplier, and restrictions.
/PSEL (Reference Pulse Input Multiplication Switch) Signal
Use the /PSEL signal to change to the reference pulse input multiplier that is set in Pn218 (Ref-
erence Pulse Input Multiplier).
Note: You must allocate the /PSEL signal to use it. You can use the following parameters to allocate the signal to a
terminal.
•
Pn50A = n.
1 (Change the sequence input signal allocations.)
•
Pn515 = n.
X
(/PSEL (Reference Pulse Input Multiplication Switching Input) Signal Allocation)
Refer to the following section for details.
6.1.1 Input Signal Allocations
/PSELA (Reference Pulse Input Multiplication Switching
Output) Signal
You can confirm if the reference pulse input multiplier was changed with the /PSELA (Reference
Pulse Input Multiplication Switching Output) signal.
Note: You must allocate the /PSELA signal to use it. You can use Pn510 = n.
X
(/PSELA (Reference Pulse
Input Multiplication Switching Output) Signal Allocation) to allocate the signal to a terminal. Refer to the fol-
lowing section for details.
6.1.2 Output Signal Allocations
Type
Signal
Connector Pin No.
Signal Status
Meaning
Input
/PSEL
Must be allocated.
ON (closed)
Enables the reference pulse input multiplier.
OFF (open)
Disables the reference pulse input multiplier.
The multiplier will be 1.
Type
Signal
Connector Pin No.
Signal Status
Meaning
Output
/PSELA
Must be allocated.
ON (closed)
The reference pulse input multiplier was
enabled.
OFF (open)
The reference pulse input multiplier was
disabled.
CAUTION
Always use the /PSELA signal to confirm that the reference pulse input multiplier has been
switched and make sure that there are no position reference pulses before you input a posi-
tion reference.
Unexpected operation may occur if position reference pulses are input before the reference
pulse input multiplier changes.