3.1 Wiring Precautions
3.1.2 Countermeasures against Noise
3
Wiring and Connection
s
3-7
Noise Filters
You must attach Noise Filters in appropriate places to protect the SERVOPACK from the
adverse effects of noise.
The following is an example of wiring for countermeasures against noise.
*1.
For the ground wire, use a wire with a thickness of at least 2.0 mm
2
(preferably, flat braided copper wire).
*2.
Whenever possible, use twisted-pair wires to wire all connections marked with
.
*3.
Refer to the following section for precautions when using Noise Filters.
Noise Filter Wiring and Connection Precautions
Noise Filter Wiring
and Connection Precautions
Always observe the following precautions when wiring or connecting Noise Filters.
•
Separate input lines from output lines. Do not place input lines and output lines in the same
duct or bundle them together.