YASKAWA
SIEPYEULA5001C LA500 Technical Manual
255
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H5-17
(11A1)
Expert
ENTER command
response @CPU BUSY
Sets operation when the EEPROM write command is sent without EEPROM write
available. Usually it is not necessary to change this setting.
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
0
(0, 1)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
0 ms
(0 - 100 ms)
H5-20
(0B57)
Communication
Parameters Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
0
(0, 1)
H5-22
(11CF)
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0
of 15DFH).
0 : Disabled
1 : Enabled
0
(0, 1)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
0045H (U1-06)
(0000H - FFFFH)
H5-27
(158B)
RUN
Function 5A Register 3
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
0042H (U1-03)
(0000H - FFFFH)
H5-28
(158C)
RUN
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register
when responding to the master device.
0049H (U1-10)
(0000H - FFFFH)
◆
H6: Pulse Train Input/Output
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H6-02
(042D)
RUN
Terminal RP Frequency
Scaling
Sets the frequency of the pulse train input signal used when the item selected with
H6-
01 [Terminal RP Pulse Train Function]
is input at 100%.
1440 Hz
(100 - 32000 Hz)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...