12.9 o: Keypad-Related Settings
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
361
■
o5-05: Log Monitor Data 3
No.
(Hex.)
Name
Description
Default
(Range)
o5-05
(1555)
RUN
Expert
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
103
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-03 [Output Current]
, set
o5-05 = 103
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-06: Log Monitor Data 4
No.
(Hex.)
Name
Description
Default
(Range)
o5-06
(1556)
RUN
Expert
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
107
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-07 [DC Bus Voltage]
, set
o5-06 = 107
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-07: Log Monitor Data 5
No.
(Hex.)
Name
Description
Default
(Range)
o5-07
(1557)
RUN
Expert
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
108
(000, 101 - 999)
Note:
Sets the number of the
U monitor
you will log.
For example, to show
U1-08 [Output Power]
, set
o5-07 = 108
. When it is not necessary to set data log monitors, set this parameter to
000
. You cannot select
U2 monitor [Fault Trace]
or
U3 Monitor [Fault History]
.
■
o5-08: Log Monitor Data 6
No.
(Hex.)
Name
Description
Default
(Setting Range)
o5-08
(1558)
RUN
Expert
Log Monitor Data 6
Sets the data log monitor. This parameter is only available when using an LCD keypad.
000
(000, 101 - 999)
Note:
Set the
U monitor
number you want to log.
For example, to display
U1-01 [Frequency Reference]
, set
o5-08 = 101
. When it is not necessary to set a data log monitor, set this
parameter to
000
. You cannot set
U2 Monitors [Fault Trace]
or
U3 Monitors [Fault History]
.
■
o5-09: Log Monitor Data 7
No.
(Hex.)
Name
Description
Default
(Range)
o5-09
(1559)
RUN
Expert
Log Monitor Data 7
Sets the data log monitor. This parameter is only available when using an LCD keypad.
000
(000, 101 - 999)
Note:
Set the
U monitor
number you will log.
For example, to show
U1-01 [Frequency Reference]
, set
o5-09 = 101
. When it is not necessary to set data log monitor, set this
parameter to
000
.
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...