YASKAWA
SIEPYEULA5001C LA500 Technical Manual
331
the output current is less than
L3-02
- 15%. When the time set in
L3-27
is expired, the drive starts acceleration
again.
Figure 12.29 Stall Prevention During Acceleration Function in OLV/PM
■
L3-02: Stall Prevent Level during Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-02
(0490)
Expert
Stall Prevent Level during
Accel
Sets the output current level at which the Stall Prevention function operates during acceleration
where the drive rated output current is 100%.
Determined by L8-38
(0 - 165%)
Note:
•
If you use a motor that is small compared to the drive and the motor stalls, decrease the setting value.
•
When you operate the motor in the constant power range, set
L3-03 [Stall Prevent Limit during Accel]
.
■
L3-03: Stall Prevent Limit during Accel
The stall prevention level set in
L3-02 [Stall Prevent Level during Accel]
is automatically reduced when the motor
is running within the constant output range. Parameter
L3-03
is the limit value used to prevent the stall prevention
level during constant output ranges to fall below the minimum required level.
Figure 12.30 Stall Prevent Level during Accel/Limit
■
L3-05: Stall Prevention during RUN
No.
(Hex.)
Name
Description
Default
(Range)
L3-05
(0493)
Expert
Stall Prevention during
RUN
Sets the function to enable and disable Stall Prevention During Run.
1
(0 - 1)
Stall Prevention function during run prevents the motor from stalling by automatically reducing the speed when
an
oL1 [Motor Overload]
occurs while the motor is running at constant speed.
Note:
An output frequency less than 6 Hz disables Stall Prevention during Run. The setting values of
L3-05
and
L3-06 [Stall Prevent Level
during Run]
do not have an effect.
0 : No
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...