130
YASKAWA
SIEPYEULA5001C LA500 Technical Manual
Figure 5.16 Safe Disable Operation
■
Switching from Usual Operation to “Safe Torque Off”
Turn OFF (open) safety input terminal H1 or H2 to enable the Safe Disable function. When the Safe Disable
function is enabled while the motor is operating, the drive output and motor torque turn off and the motor always
coasts to stop. The
b1-03 [Stopping Method Selection]
setting does not have an effect on the stopping method.
The
“
Safe Torque Off
”
status is only possible with the Safe Disable function. Clear the Run command to stop the
drive. Turning off drive output (a baseblock condition) ≠
“
Safe Torque Off
”
.
Note:
•
When it is necessary to ramp to stop the motor, do not turn off terminals H1 and H2 until the motor fully stops. This will prevent the
motor from coasting to stop during usual operation.
•
A maximum of 3 ms will elapse from when terminals H1 or H2 shut off until the drive switches to the
“
Safe Torque Off
”
status. Set the
OFF status for terminals H1 and H2 to hold for at least 3 ms. The drive may not be able to switch to the
“
Safe Torque Off
”
status if
terminals H1 and H2 are only open for less than 3 ms.
■
Going from “Safe Torque Off” to Usual Operation
The safety input will only release when there is no Run command.
•
During Stop
When the Safe Disable function is triggered during stop, close the circuit between terminals H1-HC and H2-HC
to disable
“
Safe Torque Off
”
. Enter the Run command after the drive stops correctly.
•
During Run
If you trigger the Safe Disable function during run, clear the Run command, then close the circuit between
terminals H1-HC and H2-HC to disable
“
Safe Torque Off
”
. Enter the Stop command, then enter the Run
command when terminals H1 and H2 are activated.
◆
Safe Disable Monitor Output Function and Keypad Display
Refer to
for information about the relation between the input channel status, Safety monitor output
status, and drive output status.
Table 5.10 Safe Disable Input and External Device Monitor (EDM) Terminal Status
Input Channel Status
Safety Monitor Output Status
Drive Output Status
Keypad Display
READY LED
Input 1
(H1-HC)
Input 2
(H2-HC)
MFDO Terminal
(H2-xx = 21)
MFDO Terminal
(H2-xx = 121)
ON
(Close the circuit)
ON
(Close the circuit)
OFF
ON
Baseblock
(Drive ready)
Normally displayed
READY: Illuminated
OFF
(Open)
ON
(Close the circuit)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR: Flashing
ON
(Close the circuit)
OFF
(Open)
OFF
ON
Safety status
(STo)
SToF
(Flashing)
ALM/ERR: Flashing
OFF
(Open)
OFF
(Open)
ON
OFF
Safety status
(STo)
STo
(Flashing)
READY: Flashing
■
Safety Function Status Monitor
The drive Safety monitor output sends a feedback signal about the status of the Safety function. The Safety
monitor output is one of the possible settings available for the MFDO terminals. If there is damage to the Safe
Disable circuit, a controller (PLC or safety relay) must read this signal as an input signal to hold the
“
Safe Torque
Off
”
status. This will help verify the condition of the safety circuit. Refer to the manual for the safety device for
more information about the Safety function.
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...