The overload protection detection level for the drive is automatically adjusted to the optimal value in accordance
with the setting value. Refer to
Derating Depending on Ambient Temperature on page 228
for information about
derating as specified by ambient temperature.
0 : IP20/UL Open Type
Use this setting to install IP20/UL Open Type drives.
Make sure that there is 30 mm (1.18 in) minimum of space between drives or between the drive and side of the
enclosure panel.
1 : Side-by-Side Mounting
Use this setting to install more than one drive side-by-side.
2 : IP20/UL Type 1
Use this setting to install IP20/UL Type 1 or IP55 drives.
3 : Finless Installation
Use this setting to install Finless Type drives.
■
L8-40: Carrier Freq Reduction Off-Delay
No.
(Hex.)
Name
Description
Default
(Range)
L8-40
(04F1)
Expert
Carrier Freq Reduction Off-
Delay
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
0.50 s
(0.00 - 2.00 s)
Set
L8-40 ≠ 0.00
to enable the carrier frequency reduction function during start-up. When operation starts, the
drive automatically decreases the carrier frequency. When the time set in
L8-40
is expired, the carrier frequency
returns to the value set in
C6-02 [Carrier Frequency Selection]
.
■
L8-41: High Current Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
Expert
High Current Alarm
Selection
Sets the function to cause an
HCA [Current Alarm]
when the output current is more than 150% of
the drive rated current.
0
(0, 1)
0 : No
The drive will not detect
HCA
.
1 : Yes
If the output current is more than 150% of the drive rated current, the drive will detect
HCA
.
The MFDO terminal set for an
Alarm [H2-01 to H2-03 = 10]
activates.
■
L8-42: Input Phase Loss Detection Time 2
No.
(Hex.)
Name
Description
Default
(Range)
L8-42
(04F3)
Input Phase Loss Detection
Time 2
Sets the amount of time that an Input Phase Loss condition has to be present before a fault is
triggered.
2 s
■
L8-43: Output Phase Loss Detection Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-43
(04F4)
High Current Alarm
Selection
Sets the amount of time that an Output Phase Loss condition has to be present before a fault is
triggered.
0.5 s
(0.0 - 2.0 s)
■
L8-62: Input Phase Loss Detection
No.
(Hex.)
Name
Description
Default
(Range)
L8-62
(04D8)
Input Phase Loss Detection
Sets stopping method when an input phase loss fault (PF) occurs.
0
(0 - 3)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...