SIEPYEULA5001C LA500 Technical Manual
327
12.7
L: Protection Functions
L parameters
set the following functions.
•
Motor Overload Protection
•
Operation During Momentary Power Loss
•
Stall Prevention
•
Speed Detection
•
Auto Restart
•
Detection of Overtorque/Undertorque
•
Torque Limit
•
Hardware Protection
◆
L1: Motor Protection
L1 parameters
set the motor overload protection function.
■
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name
Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
1
(0 - 3)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
•
Output Current
•
Output Frequency
•
Motor thermal characteristics
•
Time characteristics
If the drive detects motor overload, the drive will trigger an
oL1 [Motor Overload]
and stop the drive output.
Set
H2-01 = 1F [Term MA/MB-MC Function Selection = Motor Overload Alarm (oL1)]
to set a motor overload
alarm. If the motor overload level is more than 90% of the
oL1
detection level, the output terminal activates and
triggers an overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more
than one motor.
Refer to
for an example of the circuit configuration to connect more than one motor to one drive.
Figure 12.26 Protection Circuit Configuration to Connect More than One Motor to One Drive
NOTICE:
When you connect more than one motor to one drive or when the motor amp rating is higher than the drive amp
rating, set L1-01 =0 [Motor Overload (oL1) Protection = Disabled] and install thermal overload relays for each motor. The
electronic thermal protection of the drive will not function and it can cause damage to the motor.
1 : Variable Torque
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...