YASKAWA
SIEPYEULA5001C LA500 Technical Manual
259
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L8-05
(04B1)
Input Phase Loss
Protection Sel
Sets the function to enable and disable input phase loss detection.
0 : Disable
1 : Enabled
2 : St dv/dt
Depends on o2-04
(0 - 2)
L8-06
(04B2)
Input Phase Loss
Detection Level
When ripple is observed in the DC bus, expansion of the input bias is calculated and
becomes the input phase if the difference between the max and minimum values of the
ripple are greater than L8-06.
Determined by o2-04
(0.0 - 50.0%)
L8-07
(04B3)
Expert
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts
output phase loss detection when the output current decreases to less than 5% of the
drive rated current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
•
The motor rated current is very small compared to the drive rating.
•
The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1
(0 - 2)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
1
(0, 1)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0 : During Run, w/ L8-11 Off-Delay
1 : Always On
0
(0 - 1)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it
cancels the Run command when
L8-10 = 0 [Heatsink Fan Operation Selection =
During Run, w/ L8-11 Off-Delay]
.
60 s
(0 - 300 s)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the
L8-35 [Installation Method Selection]
value
changes:
•
0 [IP20/UL Open Type]
: -10 °C to +60 °C
•
1 [Side-by-Side Mounting]
: -10 °C to +50 °C
•
2 [IP20/UL Type 1]
: -10 °C to +50 °C
•
3 [Finless Installation]
: -10 °C to +50 °C
40 °C
(-10 °C - +60 °C)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease the drive overload level at which the drive will trigger
oL2
[Drive Overload]
during low speed operation (6 Hz or slower) to prevent damage to the
main circuit transistors.
Note:
Contact Yaskawa or your nearest sales representative before disabling this function
at low speeds. If you frequently operate drives with high output current in low
speed ranges, it can cause heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
1 : Enabled (Reduced oL2 Level)
1
(0, 1)
L8-18
(04BE)
Expert
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit
transistor caused by too much current.
0 : Disabled
1 : Enabled
0
(0, 1)
L8-19
(04BF)
Expert
Freq Reduction @ oH
Pre-Alarm
Sets the ratio at which the drive derates the frequency reference during an
oH
alarm.
0.8
(0.1 - 0.9)
L8-35
(04EC)
Expert
Installation Method
Selection
Sets the type of drive installation.
0 : IP20/UL Open Type
1 : Side-by-Side Mounting
2 : IP20/UL Type 1
3 : Finless Installation
Determined by o2-04
(0 - 3)
L8-40
(04F1)
Expert
Carrier Freq Reduction
Off-Delay
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
0.50 s
(0.00 - 2.00 s)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...