Chapter 6.
OPERATION
6 - 1
Turning the Power ON
6-1
The DCP32 is not equipped with a power switch or protective fuses. If necessary, prepare these externally. When a
voltage of 90 to 264 Vac is applied across terminals
1
and
2
on the DCP32, the display appears for about ten
seconds after which control and other operations are started. During initialization of the controller until start of
operations, the LEDs on the profile display light successively at uneven intervals clockwise from top right.
The following diagram shows the flow of operations at startup.
●
Startup flow
Power ON
RAM backup normal?
NO
YES
Check start of general reset
Parameter = factory shipment setting
Delete entire program.
Program operation mode
READY mode
AUTO mode
Program No. = 1/segment No. = 1
Segment progress time = 0
Continuation of program operation/constant-value operation modes
Continuation of READY/RUN/HOLD/FAST/END modes
Continuation of AUTO/MANUAL modes
(Continuation of manual value if in MANUAL mode)
Continuation of program No./segment No.
Continuation of segment progress time
Continuation of display No. of basic display state in AUTO mode
Cancellation of auto-tuning/smart-tuning
Cancellation of MFB automatic adjustment by 2G output
Initiallization of G.Soak standby time
Initialization of PID operation
Initialization of event output state
Setting display state
→
Basic display state
Display No. of basic display state in MANUAL mode
Start of operations
Press ENT key.
Handling Precautions
With the following modes and items, the state that was active when the
power was turned OFF continues when the power is turned back ON.
• READY, RUN, HOLD, FAST, END modes
• AUTO, MANUAL modes
• MANUAL values in the MANUAL mode
• Program No., segment No.
• Progress time in segment
• Display No. if in basic display state in the AUTO mode