7-23
Chapter 7. PARAMETER SETUP
Setting
0: Standby OFF
1: Standby ON
[Note]
The controller stands by after power is restored and in the
READY mode. When the event type setting is
≥
50, “- - - -” is
displayed and setting is not possible.
0 to 200U (when event type is neither MV nor MFB)
0.0 to 20.0% (when event type is MV or MFB)
[Note]
When the event type setting is
≥
50, “- - - -” is displayed and
setting is not possible.
0 to 3600 seconds
0: T1 to T5 are all time events.
1: T1 is a segment No. event.
T2 to T5 are time events.
2: T1 and T2 are segment No. events.
T3 to T5 are time events.
3: T1 to T3 are segment No. events.
T4 and T5 are time events.
4: T1 to T4 are segment No. events.
T5 is a time event.
5: All T1 to T5 are segment No. events.
[Note]
On models not supporting time events, “- - - -” is displayed and
setting is not possible.
Settings can be changed only in the READY mode.
No. Item Code
Item
10
Ed3
Event 3 standby
11
HYS3
Event 3 hysteresis
12
dL3
Event 3 ON delay time
13
tt
Time event type
Factory
Setting
0
5
0
0
User
Setting