7-47
Chapter 7. PARAMETER SETUP
Setting
0: Program operation
1: Constant-value operation
[Note]
This setting can be changed only in the READY mode.
This setting can be set in the SP1 lower to upper limit range in
setup data settings
C09 and C10.
This setting can be set in the SP2 lower to upper limit range in
setup data settings
C32 and C33.
-1999 to +9999U
(event type is PV, deviation or SP)
0 to 9999U
(event type is absolute value deviation)
-10.0 to +110.0%
(event type is MV or MFB)
[Note]
When the event configuration data type setting is
≥
50 for each
event, “- - - -” is displayed and setting is not possible.
[Note]
“- - - -” is displayed and setting is not possible.
P. : 0.1 to 999.9%
I. : 0 to 3600 seconds. 0 disables integral action.
d. : 0 to 1200 seconds. 0 disables derivative action.
oL.: -10.0 to MV upper limit %
oH.: MV lower limit to +110.0%
rE. : 0.0 to 100.0%
br. : 0 to 30 0 disables the brake function.
dP.: 0.1 to 999.9%
dI. : 1 to 3600 seconds
dd.: 0 to 1200 seconds
[Note]
• These parameters are used for control of CH1.
• When CH1 is used primarily for SP (setup data
C18 setting is
1), “- - - -” is displayed and setting is not possible.
• When variable parameter
m-C setting is 2 (estimated position
control only) on 2G output models and setup data
C44 setting
is 0, “- - - -” is displayed for items
oL. and oH., and setting is
not possible.
• When
I setting is not 0, “- - - -” is displayed for rE. and setting
is not possible.
• When variable parameter
St setting is 0 (smart-tuning
disabled), “- - - -” is displayed for
br. and setting is not
possible.
• When variable parameter
2PId setting is 0 (2 degrees of
freedom PID disabled), “- - - -” is displayed for
dP., dI., dd.
and setting is not possible.
• “- - - -” is displayed and setting is not possible for the
P.-C to
rE.-C items in the following instances:
- On models other than heat/cool models
- On heat/cool models and setup data
C44 is set to 1
- On 3D output models and setup data
C45 is set to 1
For details, see the Note for PID parameters.
[Note]
“- - - -” is displayed and setting is not possible.
No. Item Code
Item
1
modE
Operation mode
2
SP
SP1
3
SP2
SP2
4
Ev1
Event 1 setting value
5
Ev2
Event 2 setting value
6
Ev3
Event 3 setting value
7
—
Unused
8
—
Unused
9
—
Unused
10
—
Unused
11
P.
Proportional band (CH1)
12
I.
Reset time (CH1)
13
d.
Rate time (CH1)
14
oL.
MV lower limit (CH1)
15
oH.
MV upper limit (CH1)
16
rE.
Manual reset (CH1)
17
br.
Brake (CH1)
18
dP.
Disturbance inhibit
proportional band (CH1)
19
dI.
Disturbance inhibit reset
time (CH1)
20
dd.
Disturbance inhibit rate
time (CH1)
21
P.-C
Proportional band
(for CH1 cool control)
22
I.-C
Reset time
(for CH1 cool control)
23
d.-C
Rate time
(for CH1 cool control)
24
oL.-C
MV lower limit
(for CH1 cool control)
25
oH.-C
MV upper limit
(for CH1 cool control)
26
rE.-C
Manual reset (for CH1
cool control)
27
—
Unused
28
—
Unused
29
—
Unused
30
—
Unused
Factory
Setting
0
0
0
9999
9999
9999
—
—
—
—
100.0
0
0
0.0
0.0
50.0
0
100.0
120
0
100.0
0
0
0.0
100.0
50.0
—
—
—
—
User
Setting
■
Constant-value operation data settings “
CnSt
”