7-35
Chapter 7. PARAMETER SETUP
Setting
-1999 to +9999U
-1999 to +999.9%
[Note]
When auxiliary output is not supported, “- - - -” is displayed and
setting is not possible.
When the auxiliary output type is MV or MFB, the unit is %.
Otherwise, the unit is U.
0: NOP
1: Fast operation
2: PV start (CH1)
3: NOP
4: ST start/stop (CH1)
5: NOP
6: Auto/manual (CH1)
7: Cancel G.Soak by OR conditions
8: Cancel G.Soak by AND conditions
9: Direct/reverse action inversion (CH1)
10: NOP
11: NOP
12 PV start (CH2)
13: NOP
14: AT start/stop (CH2)
15: NOP
16: Auto/manual (CH2)
17: NOP
18: NOP
19: Direct/reverse action inversion (CH2)
20: NOP
[Note]
On external switch 4-input models, “- - - -” is displayed and
setting is not displayed.
When the same assignment is set to two or more RSWs, the
RSW setting with the lowest No. is valid.
When this setting is set to NOP, the controller state is not
switched by external switch input ON/OFF. The controller state
can be switched ON/OFF by communications.
1000 to 5000
[Note]
To set the No., add the No. of the item to be assigned to PARA
key to the following values for the setting group containing that
item.
• 1000:
Constant-value operation data
• 1500:
PID parameter 1
• 2000:
PID parameter 2
• 2500:
Variable parameter
• 3000:
Variable parameter 2
• 3500:
Event configuration data
• 4000:
Table data
• 4500:
Setup data
Assignments to which a nonexistent No. have been set are
invalid.
0: READY
1: END
0: Hours/minutes
1: Minutes/seconds
0: Remaining segment time
1: Total operation time
[Note]
The total operation time returns to 0 in the READY mode.
0: ON
1: PV1 OFF
2: PV2 OFF
3: PV1, PV2 OFF
No. Item Code
Item
50
C50
Auxiliary output lower
limit (4 mA)
51
C51
Auxiliary output upper
limit (20 mA)
52
C52
External switch input
RSW5 assignment
53
C53
External switch input
RSW6 assignment
54
C54
External switch input
RSW7 assignment
55
C55
PARA key assignment
item 1
56
C56
PARA key assignment
item 2
57
C57
PARA key assignment
item 3
58
C58
PARA key assignment
item 4
59
C59
PARA key assignment
item 5
60
C60
PARA key assignment
item 6
61
C61
PARA key assignment
item 7
62
C62
PARA key assignment
item 8
63
C63
Operation completion
state
64
C64
Program time unit
65
C65
Time display
66
C66
PV display
Factory
Setting
0
1000
0
0
0
1000
1000
1000
1000
1000
1000
1000
1000
0
0
0
0
User
Setting