![Yamatake DigitroniK DCP32 Скачать руководство пользователя страница 168](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225168.webp)
8-20
Chapter 8. PROGRAM SETUP
8 - 3
General Reset
A general reset can be executed when the DCP32 is in the READY AUTO mode in the basic display state. If the
DCP32 is not in the basic display state, press the
DISP
key.
A “general reset” involves the following operations:
• Clearing all program setups for program Nos.1 to 19
• Returning parameter setups to their factory settings
• Changing the mode to the program operation READY AUTO mode
■
Operation
①
Set the DCP32 to the READY AUTO mode.
Set variable parameter
LoC
and
PrtC
to 0.
②
If you press the
FUNC
key + the
CLR
key + the
DISP
key in the basic display
state, the display changes to confirm execution of general reset, and “
g.rES
” is
displayed on the upper display.
③
If you press the
ENT
key, the general reset is executed, and operation starts
from initialization when the power is turned ON.
If you press the
DISP
key, general reset is not executed, and the DCP32 returns
to the basic display state.
●
Display
In the constant-value operation mode, all of the program No., segment No. and
profiles displays are cleared.
• If a RAM backup error occurs when the power is turned ON, the display changes
to confirm general reset without pressing any of the keys on the console, and
“
g.rES
” is displayed in the upper display.
If you press the
ENT
key, the general reset is executed. Other keys, however,
cannot be operated.
• The following setup data items are not returned to their factory settings.
C02, C03
:
Save setting values.
C04, C05
:
These are set to 0 when the input 1 range type is set to linear.
C06
:
This is set to 1000 when the input 1 range type is set to linear.
C22, C23
:
Save setting values.
C24, C25
:
These are set to 0 when the input 2 range type is set to linear.
C26:
This is set to 1000 when the input 2 range type is set to linear.
C75, C76, C77
: Save setting values.
However, note that if a RAM backup error occurs when the power is turned ON,
C02, C03, C22, C75, C76
and
C77
settings become 0 and
C23
setting
becomes 128.
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5