5-7
Chapter 5. FUNCTIONS
• If the ON time is set to 0 in the case
of G.Soak standby, output becomes
ON from the G.Soak standby state,
and the ON time is started at
completion of the G.Soak standby
time.
The output time = G.Soak standby
time + OFF time
(See segment 8 in the figure.)
• ON and OFF time settings the same
time as the segment end point are
valid in the case of the final
segment END mode.
(See segment 10 in the figure.)
●
Segment No. events
The current segment No. is output as binary code.
When all of
T1
to
T5
are selected as segment No. events in the time event type
setup, all ON-OFF operations are as shown in the following table.
When
T1
to
T4
are assigned partially to segment No. events, only the assigned
time events operate as shown in the following table, and the remaining events
operate as regular time events.
8
G.Soak standby
Segment 8 time start
When ON = 0, output turns ON
when segment 8 is entered.
Segment
ON time
OFF time
Output ON
Output OFF
9
ON = segment time
10
Segment time
END mode
ON = segment time
Segment
ON time
OFF time
Output ON
Output OFF
Segment
ON time
OFF time
Output ON
Output OFF
Segment No.
Event No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
T1
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
T2
OFF ON
ON OFF OFF ON
ON OFF OFF ON
ON OFF OFF ON
ON
T3
OFF OFF OFF ON
ON
ON
ON OFF OFF OFF OFF ON
ON
ON
ON
T4
OFF OFF OFF OFF OFF OFF OFF ON
ON
ON
ON
ON
ON
ON
ON
T5
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
Segment No.
Event No.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
T1
OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
T2
OFF OFF ON
ON OFF OFF ON
ON OFF OFF ON
ON OFF OFF ON
T3
OFF OFF OFF OFF ON
ON
ON
ON OFF OFF OFF OFF ON
ON
ON
T4
OFF OFF OFF OFF OFF OFF OFF OFF ON
ON
ON
ON
ON
ON
ON
T5
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON