7-36
Chapter 7. PARAMETER SETUP
Setting
0: Display ON
1: Display OFF
[Note]
Even when set to 1, alarm-related events do not operate.
0: Display ON
1: Display OFF
[Note]
Even if each of the items are set to 1, the function operates if
data is set to the program.
On models not supporting time events, time event items are not
displayed in program settings regardless of the number of
C69
settings.
0: Compensated internally
1: Compensated externally
[Note]
When both input 1 range type and input 2 range type are other
than a thermocouple, “- - - -” is displayed and setting is not
possible.
0: Upscale
1: Downscale
[Note]
This setting is valid when the input 1 range type is
thermocouple, resistance temperature detector or linear (mV
series).
0: Input ON again enabled within time-proportional cycle
1: Input ON again disabled within time-proportional cycle
[Note]
When any of outputs 1, 2 or 3 are not voltage time-proportional
outputs, “- - - -” is displayed and setting is not possible.
0: Current output
1: Voltage output
[Note]
When each of the outputs are relay output, position-
proportional output, auxiliary output or output is not mounted, “-
- - -” is displayed and setting is not possible.
2 to 22 mA
[Note]
When each of the outputs are other than voltage output
(including heat/cool), “- - - -” is displayed and setting is not
possible.
Normally, use the factory setting.
0: Burnout current ON
1: Burnout current OFF
[Note]
Normally set to “0”.
When radiamatic temperature detector RT50 is connected to
input 1, use at setting 1.
0: Expansion disabled
1: Expansion enabled
[Note]
This setting is for service use only. Normally set to 0.
[Note]
“- - - -” is displayed and setting is not possible.
0 to 127
[Note]
On models not supporting communications, or when steup data
C97 setting is not 0, “- - - -” is displayed and setting is not
possible.
0 disables communications.
No. Item Code
Item
67
C67
Alarm display
68
C68
Programming item:
Events 1 to 3
69
C69
Programming item: Time
events 1 to 5
70
C70
Programming item: PID
set, G.Soak
71
C71
Programming item: PV
start, cycle, pattern link
72
C72
Cold junction
compensation
73
C73
Input operation at input 1
disconnection
74
C74
Voltage time-
proportional output
system
75
C75
Output 1 selection
76
C76
Output 2 selection
77
C77
Output 3 selection
78
C78
Voltage output 1
adjustment
79
C79
Voltage output 2
adjustment
80
C80
Voltage output 3
adjustment
81
C80
Input 1 burnout current
(Expansion setting 1)
82
C82
Expansion setting 2
83
C83
Unused
84
C84
CPL communications
address
Factory
Setting
0
0
0
0
0
0
0
0
0
0
0
15
15
15
0
0
—
0
User
Setting