7-8
Chapter 7. PARAMETER SETUP
Setting
0.5 to 25.0%
[Note]
This setting is displayed on 2G output models.
On 2G output model and models other than heat/cool models,
“- - - -” is displayed and setting is not possible.
-100.0 to +50.0%
[Note]
This setting is displayed on heat/cool models.
On 2G output model and models other than heat/cool models,
“- - - -” is displayed and setting is not possible.
5 to 120 seconds (relay output)
1 to 60 seconds (voltage output)
[Note]
On models whose output 1 is neither relay output nor voltage
output, “- - - -” is displayed and setting is not possible.
5 to 120 seconds (relay output)
1 to 60 seconds (voltage output)
[Note]
On models whose output 2 is neither relay output nor voltage
output, “- - - -” is displayed and setting is not possible.
[Note]
“- - - -” is displayed and setting is not possible.
1 to 60 seconds
[Note]
On models whose output 3 is not voltage output, “- - - -” is
displayed and setting is not possible.
0 to 1000U
[Note]
On models other than 3D output models, “- - - -” is displayed
and setting is not possible.
0: MFB control (conventional) + estimated position control
1: MFB control (conventional) only
2: Estimated position control only
[Note]
On models other than 2G output models, “- - - -” is displayed
and setting is not possible.
0: Adjustment disabled
1: Adjustment enabled
[Note]
On models other than 2G output models, “- - - -” is displayed
and setting is not possible.
On 2G output models, when
m-C setting is 2, “- - - -” is
displayed and setting is not possible.
0 to (fully open adjustment - 500)
[Note]
On models other than 2G output models, “- - - -” is displayed
and setting is not possible.
On 2G output models, when
m-C setting is 2, “- - - -” is
displayed and setting is not possible.
(fully closed adju 500) to 9999
[Note]
On models other than 2G output models, “- - - -” is displayed
and setting is not possible.
On 2G output models, when
m-C setting is 2, “- - - -” is
displayed and setting is not possible.
5.0 to 240.0 seconds
[Note]
On models other than 2G output models, “- - - -” is displayed
and setting is not possible.
No. Item Code
Item
21
dIFF
Position-proportional
dead zone
Heat/cool control dead
zone
22
CY.1
Output 1 time-
proportional output cycle
23
CY.2
Output 2 time-
proportional output cycle
24
CY.3
Output 3 time-
proportional output cycle
25
dv-L
3-position control
deviation lower limit
26
dv-H
3-position control
deviation upper limit
27
HY-L
3-position control lower
limit hysteresis
28
HY-H
3-position control upper
limit hysteresis
29
m-C
Motor control method
selection
30
m-At
Motor valve opening
automatic adjustment
31
m-CL
Motor valve opening
adjustment fully closed
position
32
m-oP
Motor valve opening
adjustment fully open
position
33
m-t
Motor valve opening
adjustment fully
open/closed time
Factory
Setting
5.0
0.0
10
10
10
5U
5U
5U
5U
0
0
1000
9000
30.0