Chapter 9. MAINTENANCE & TROUBLESHOOTING
●
Pressing the PROG key + the RUN/HOLD key does not reset the DCP32.
“Reset in the program operation mode” refers to switching to the READY mode
and returning to the No.1 segment.
“Reset in the constant-value mode” refers to switching to the READY mode.
●
Pressing the PROG key + the DISP key does not advance the program.
●
Pressing the FUNC key + the
→
key does not change the DCP32 to the FAST mode.
●
Pressing the A/M key does not change the DCP32 to the AUTO mode.
●
Pressing the A/M key does not change the DCP32 to the MANUAL mode.
Remedy
Press RUN/HOLD key to set the DCP32 to the RUN mode. (The
DCP32 can be reset in case of external switch input or communi-
cations even in the READY mode.)
Set variable parameter
LoC setting to 0 to 2.
Cause
The DCP32 is in the READY mode.
Key lock is enabled.
Remedy
Press RUN/HOLD key to set the DCP32 to the RUN mode. (The
DCP32 can be reset in case of external switch input or communi-
cations even in the READY mode.)
Reset the DCP32 (PROG + RUN/HOLD key) to set it to the
READY mode, and press RUN/HOLD key again to set it to the
RUN mode.
Set constant-value operation data
modE setting to 0.
Set variable parameter
LoC setting to 0 to 2.
Cause
The DCP32 is in the READY mode.
The DCP32 is in the END mode.
The DCP32 is in the constant-value operation mode.
Key lock is enabled.
Remedy
Press RUN/HOLD key to set the controller to the RUN mode.
Reset the DCP32 (PROG + RUN/HOLD key) to set it to the
READY mode, and press RUN/HOLD key again to set it to the
RUN mode.
Set constant-value operation data
modE setting to 0.
Set variable parameter
LoC setting to 0 to 2.
Cause
The DCP32 is in the READY mode.
The DCP32 is in the END mode.
The DCP32 is in the constant-value operation mode.
Key lock is enabled.
Remedy
Set setup data
C45 setting to 0 and switch to PID control from 3-
position-proportional control.
Set variable parameter
LoC setting to 0 to 2.
Cause
3-position-proportional control is selected on a 3D out-
put model.
Key lock is enabled.
Remedy
Set variable parameter
LoC setting to 0 to 2.
Cause
Key lock is enabled.