![Yamatake DigitroniK DCP32 Скачать руководство пользователя страница 157](http://html.mh-extra.com/html/yamatake/digitronik-dcp32/digitronik-dcp32_user-manual_905225157.webp)
8-9
Chapter 8. PROGRAM SETUP
• When the ON time is set to 99:59, “- - - -” is displayed as the OFF time, and the
display does not blink. In this case, the OFF time cannot be set.
• When the ON time is set higher than the time setting of the pattern item, event
output at that segment is OFF. However, note that event output is ON when the
mode changes to the END mode at segments whose ON time and pattern item
time are equal.
• The profile display displays the trend of the SP pattern on the channel currently
selected in the basic display state.
■
Setting up PID set No. (CH1) items
①
In the setting display state, move to the PID set No. (CH1) items of the segment
to be set up on the programming map.
②
If you press the
ENT
key, the lower display starts blinking to indicate start of
entry to the No.1 setup.
③
Press the
↑
,
↓
,
←
or
→
key to set to the No.1 setup PID set No. setting.
Setting range: 0 to 8 (non heat/cool models, or when setup data
C44
setting is
1)
0 to 4 (heat/cool models and setup data
C44
setting is 0)
④
When you press the
ENT
key, blinking on the upper display stops.
●
Display
• When setup data
C11
is set to 1 and PID set auto-switching ON (CH1) is
selected, the PID set No. (CH1) items on the programming map are skipped and
not displayed.
• On models whose CH1 output is current output, when setup data
C18
is set to 1
and the DCP32 is selected for use as a programmer, the PID set No. (CH1)
items on the programming map are skipped and not displayed.
• On 3D output models, when setup data
C44
is set to 0 and
C45
is set to 1, and
3-position control is selected on channel 1, the PID set No. (CH1) items on the
programming map are skipped and not displayed.
• When setup data
C70
is set to 1, the PID set No. (CH1) items on the
programming map are all skipped and not displayed.
• When the PID set No. (CH1) setting is set to 0, this means that the PID set No.
(CH1) of the previous segment is continued. When the PID set No. (CH1)
setting is set to 0 in the No.1 segments, this is the same as being set to 1.
• The profile display displays the trend of the SP pattern on the channel currently
selected in the basic display state.
PID set No. (CH1) setting value
PROG
SEG
PROFILE
Program
No.
Segment
No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out